64
FB55
At pressure closed-loop
mode, limit time when
motor reverse running
0
~
50.0
10.0
√
√
√
FB56
Rotating Resolver testing
filtering
2
~
100
10
√
√
√
FB57
Rotating Resolver fault
testing enable
0: Invalid 1: Valid
1
√
√
√
FB58
Reverse running limit
enable
0: Invalid 1: Valid
1
√
√
√
FB59
Time of pressure sensor
test fault
0~100.0 (Invalid when it is
set to 0)
3.0
√
√
√
FB63
AI1
filtering
time
constant
0
~
255 (Invalid when it is
set to 0)
0
√
√
√
FB64
AI2
filtering
time
constant
0
~
255 (Invalid when it is
set to 0)
0
√
√
√
FB65
AI3
filtering
time
constant
0
~
255 (Invalid when it is
set to 0)
0
√
√
√
FB69
flux-weakening
coefficient
0.01
~
5.00
0.20
√
√
√
FB76
Whether injection signal
is valid
0: invalid 1: valid
1
√
√
√
FB77
Injection signal input
logic
0: Positive logic (common
open)
1: Negative logic (common
closed)
0
√
√
√
FB79
Inhibition
pressure
overshoot coefficient 1
0
~
50
Subject to model
√
√
√
FB80
Inhibition
pressure
overshoot coefficient 2
0
~
50
Subject to model
√
√
√
FB83
Poles position study with
load
0: Disable 1: Enable
0
╳
√
√
FB84
Speed limit coefficient
during pressure-holding
process
0~500
Subject to model
√
√
√
Function code
Function definition
Setting range
Mfr’s value
Change
Copy
all
Copy in
part
FC00
Master/auxiliary pump
selection
0:auxiliary pump
1: master pump
2
: oscilloscope output
0
╳
╳
╳
FC01
The
numbers
of
auxiliary pumps
The number of auxiliary
pumps to be set in the master
pump drive. If no aux pump,
please set the numbers to
zero.
0
╳
√
√
FC02
Master pump capacity
Unit
:
mL/r
1
~
260
1
╳
√
√
FC03
Capacity of auxiliary
pump 1 unit: mL/r
1
~
260
1
╳
√
√
FC04
Capacity of auxiliary
pump 2 unit: mL/r
1
~
260
1
╳
√
√