ERR4
Current zero
excursion
malfunction
*Flat cable is loosened.
*Current detector is broken.
*check the flat cable.
*ask for help from manufacture.
PP-1
Pressure sensor
fault
*Pressure sensor damaged;
*Pressure sensor oil outlet blocks up;
* Pressure sensor power malfunction;
*The wiring between pressure sensor
and servo drive disconnected.
*FA19 is not set correctly
*replace pressure sensor;
*check and dredge oil outlet;
* check if pressure sensor power is normal;
*check the wiring between pressure sensor and servo
drive
*check pressure sensor zero drift.
PP-2
Pump reversal
running fault
*Pressure sensor damaged;
*Feedback pressure is higher than
given pressure.
*replace pressure sensor;
*check pressure analog voltage.
PGo
Protection of
resolver
*Motor feedback Resolver base is not
welded well
*Resolver cable damaged;
* Resolver interface of control board
is damaged.
*check the Resolver base weld.
*replace the Resolver wiring
*ask for help from manufacture.
Tro
KTY84
disconnected
protection
Servo drive can not detect KTY84.
*check the cable.
*check whether resistor detecting temperature is normal.
AL05
Resolver
commutation fault
*Commutation not checked.
* Motor sequence is wrong.
*Pump or motor is locked-rotor, or
motor speed is lower than 5 rpm.
*Please set F822=1 to check commutation.
*Please change the sequence of two phase and check
commutation
*Exclude locked-rotor fault or increase speed to higher
than 5rpm.
AL14
Braking unit fault
*Braking circuit fault
*Power voltage is too high.
*ask for help from manufacture;
*Decrease power voltage or adjust the value of F611.
FER1
Analog voltage
corresponding to
multi-point
pressure is wrong
* FA32
~
FA41 set wrongly
* FA32
~
FA41 value must be set from small to large.
FER2
Multi-point
pressure fault
* FA42
~
FA52 set wrongly
* FA42
~
FA52 value must be set from small to large.
FER3
Analog voltage
corresponding to
multi-point flow is
wrong
* FA54
~
FA63 set wrongly.
* FA54
~
FA63 value must be set from small to large.
FER4
Multi-point flow
fault
* FA64
~
FA75 set wrongly.
* FA64
~
FA75 value must be set from small to large.
Er71
Copy timeout
* No effective data is received in 3
seconds during copy process.
*Check the connection of copy unit.
Er72
Copy in running
process
*Copy while servo drive is in running
or fault status.
*Stop or reset servo drive.
Er73
Copy while
password is not
entered
User’s password is valid and not
entered.
*Check and modify the value of F638 according to
requirement.
Er74
Copy while model
is different
Copy is forbidden when copy code,
voltage rating or power is different.
*Copy code should be same as copy unit.
*Voltage and power should be same as copy unit.