![Parker IM20 Series Скачать руководство пользователя страница 37](http://html.mh-extra.com/html/parker/im20-series/im20-series_product-manual_756258037.webp)
37
pressure sensor fault will occur and servo drive stops and trip into PP-1.
FB60 is used to set pressure feedback threshold, if pressure feedback value is always lower than setting value, pressure
feedback sensor fault will occur.
FB61 is the current threshold, if the current is higher than this value, servo drive will start to check whether
pressure feedback sensor has fault.
FB62 is duration time after servo drive detects pressure sensor fault.
5.6.6 Motor parameters
Function code
Definition
Setting range
Mfr's value
Note
F800
Motor’s parameters
measurement
0:invalid
1: motor parameter
auto-tuning, motor
resistor , D-axis and
Q-axis inductance,
Resolver installation
angle
2: motor parameter
auto-tuning, motor
resistor , D-axis and
Q-axis inductance,
Resolver installation
angle, back-EMF
0
╳
F801
Rated power
0.4
~
315KW
Subject to model
×
F802
Rated voltage
220
~
460V
380
×
F803
Rated current
0.1
~
6500A
Subject to model
×
F804
Number of motor poles
2
~
100
8
×
F805
Rated rotary speed
1
~
4000
Subject to model
×
F806
Maximum rotary speed
1
~
4000
Subject to model
×
F807
Motor series
0~7
Subject to model
F808
HAITIAN and PHASE
motor series selection
0~23
F810
Motor rated frequency
1
~
300
Subject to model
×
F813
Rotary speed loop
KP
0.01
~
50.00
Subject to model
√
F814
Rotary speed loop
KI
0.01
~
10.00
Subject to model
√
F815
d axis inductance
0~9999
Subject to model
×
F816
Back EMF voltage
(corresponding to
maximum rotary speed)
0~9999
Subject to model
×
F817
Poles position
compensation value
0
~
100
25
×
F822
Poles position study
0, 1
0
×
F907
Quadrature axis
inductance
0~20.00
Subject to model
×
Содержание IM20 Series