C h a p t e r 3 : I n s t a l l i n g t h e D r i v e
3-35
AC890PX AC Drive
80.01 AUTOTUNE
ENABLE
0 : FALSE
1 : TRUE
Set TRUE to enable
Autotune. Resets to FALSE
when complete.
x
80.02 AUTOTUNE MODE
0 : ROTATING
1 : STATIONARY
2 : SPD LOOP
ROTATING
3 : SPD LOOP
STATIONARY
Set the type of Autotune.
x
x
27.06 MAG CURRENT
product code dependent
Rotating Autotune sets
actual value
Enter the No-Load Amps
from the motor nameplate
x x x
27.14 STATOR RES
product code dependent
Autotune sets actual
value
Motor per-phase stator
resistance
x x
27.15 LEAKAGE INDUC
product code dependent
Autotune sets actual
value
Motor per-phase stator
leakage inductance
x x
27.16 MUTUAL INDUC
product code dependent
Autotune sets actual
value
Motor per-phase stator
mutual (magnetising)
inductance
x x
27.17 ROTOR TIME
CONST
product code dependent
Autotune sets actual
value
The motor model rotor
time constant as
determined by Autotune
x x
78.01 SPEED PROP GAIN
20.0
Sets the proportional gain
of the loop
x x
x
78.02 SPEED INT TIME
100 ms
The integral time constant
of the speed loop
x x
x
Содержание AC890PX Series
Страница 8: ......
Страница 12: ...1 4 C h a p t e r 1 G e t t i n g S t a r t e d AC890PX AC Drive...
Страница 17: ...C h a p t e r 2 P r o d u c t O v e r v i e w 2 5 AC890PX AC Drive 890PX bottom wire entry...
Страница 22: ...2 10 C h a p t e r 2 P r o d u c t O v e r v i e w AC890PX AC Drive...
Страница 74: ...4 8 C h a p t e r 4 A s s o c i a t e d E q u i p m e n t AC890PX AC Drive...
Страница 96: ...5 22 C h a p t e r 5 O p e r a t i n g t h e D r i v e AC890PX AC Drive...
Страница 162: ...8 22 C h a p t e r 8 T r i p s F a u l t F i n d i n g AC890PX AC Drive...
Страница 170: ...9 8 C h a p t e r 9 R o u t i n e M a i n t e n a n c e R e p a i r AC890PX AC Drive...
Страница 286: ...D 84 A p p e n d i x D P r o g r a m m i n g AC890PX AC Drive Functional Description...