![Parker AC890PX Series Скачать руководство пользователя страница 93](http://html2.mh-extra.com/html/parker/ac890px-series/ac890px-series_engineering-reference_3836877093.webp)
C h a p t e r 5 : O p e r a t i n g t h e D r i v e
5-19
AC890PX AC Drive
Using Motor Chokes (output)
Motor chokes may be used with the 380V/460V and 500V/575V AC890PX AC Drive.
Installations with long cable runs may suffer from nuisance overcurrent trips. A choke may be fitted in the drive output to
limit capacitive current. Screened cable has a higher capacitance and may cause problems in shorter runs. A choke may be
used on cable lengths of over 100m.
Motor Choke
Maximum Operating Current
Parker SSD Drives Part Number
250A CO471702U250
320A CO471702U320
400A CO471702U400
500A CO471702U500
600A CO471702U600
750A CO471702U750
Contact Parker SSD Drives for recommended choke values.