E-59
Technical Specifications
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
Internal Dynamic Brake Switch (Frame F)
Model Number
(Europe)
Motor
Power
(kW/hp)
Brake Switch
Peak Current
(A)
Peak Brake
Dissipation
(kW/hp)
Brake Switch
Continuous
Current (A)
Continuous
Brake
Dissipation
(kW/hp)
Minimum
Brake Resistor
Value
(
Ω
)
20s maximum, 25% duty
400V Build Variant: 380-460V ±10%, 45-65Hz
DC link brake voltage: 750V
890SD-433105F...
55/75
94
62/83
25
18/25
8
890SD-433145F... 75/100
125
90/125
32
24/32
6
890SD-433156F... 90/125
136
102/137
32
24/32
5.5
890SD-433180F... 90/150
136
102/137
32
24/32
5.5
500V Build Variant: 500V ±10%, 45-65Hz
DC link brake voltage: 820V
890SD-533105F...
55/75
82
68
25
20.5/27
10
890SD-533145F... 75/100
102
83
31
25.5/34
8
890SD-533156F... 90/125
102
83
31
25.5/34
8