Sequencing Logic
B-12
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
Communications Status
The COMMS STATUS parameter (PREF 95.08) in the COMMS CONTROL function block monitors the
sequencing of the Drive. It is a 16-bit word based on standard fieldbus drive profiles. Some bits are not
implemented in the initial release and are set to 0 (see “Supported” column of the table below).
Bit Name
Description
Supported
0 Ready To Switch On
1 Switched On
Ready for operation (refer control bit 0)
2 Operation Enabled
(refer control bit 3)
3 Fault
Tripped
4 (Not) Voltage Disabled OFF 2 Command pending
5 (Not) Quick Stop
OFF 3 Command pending
6 Switch On Disable
Switch On Inhibited
7 Warning
8 SP / PV in Range
9 Remote
= 1 if Drive will accept Command Word
10 Setpoint Reached
= 1 if not ramping
11 Internal Limit Active
= 1 if current limit active or speed loop is in torque
limit