Programming
D-11
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
ANALOG OUTPUT
SETUP::INPUTS & OUTPUTS::ANALOG OUTPUT
The analog output blocks converts the demand percentage into a form suitable for driving the analog output electronics of the
Drive.
Parameter Descriptions
VALUE
PREF: 6.01, 7.01,
Default: —.xx %
Range: -300.00 to 300.00 %
The demanded value to output.
TYPE
PREF: 6.05, 7.05
Default:0..+10V
Range: See below
The output hardware Voltage type. An incorrect selection will force the VALUE to be set to zero.
Enumerated Value
:
Type
0 : -10..+10 V
1 : 0..10 V
Functional Description
The Drive has two analog outputs. There is an ANALOG OUTPUT function block associated with each of these:
AOUT1 is associated with terminal X12/06
AOUT2 is associated with terminal X12/07
OUTPUT
VALUE
TYPE