Parameter Reference
C-241
AC30 series Variable Speed Drive
0426 VHz User Freq[2]
Parameters::Motor Control::Fluxing VHz
REAL
20.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01379
0427 VHz User Freq[3]
Parameters::Motor Control::Fluxing VHz
REAL
30.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01381
0428 VHz User Freq[4]
Parameters::Motor Control::Fluxing VHz
REAL
40.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01383
0429 VHz User Freq[5]
Parameters::Motor Control::Fluxing VHz
REAL
50.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01385
0430 VHz User Freq[6]
Parameters::Motor Control::Fluxing VHz
REAL
60.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01387
0431 VHz User Freq[7]
Parameters::Motor Control::Fluxing VHz
REAL
70.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01389
0432 VHz User Freq[8]
Parameters::Motor Control::Fluxing VHz
REAL
80.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01391
0433 VHz User Freq[9]
Parameters::Motor Control::Fluxing VHz
REAL
90.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01393
0434 VHz User Freq[10]
Parameters::Motor Control::Fluxing VHz
REAL
100.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01395
0435 VHz User Volts
Parameters::Motor Control::Fluxing VHz
ARRAY[0..10]
STOPPED ENGINEER
01397
0436 VHz User Volts[0]
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01399
0437 VHz User Volts[1]
Parameters::Motor Control::Fluxing VHz
REAL
10.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01401
0438 VHz User Volts[2]
Parameters::Motor Control::Fluxing VHz
REAL
20.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01403
0439 VHz User Volts[3]
Parameters::Motor Control::Fluxing VHz
REAL
30.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01405
0440 VHz User Volts[4]
Parameters::Motor Control::Fluxing VHz
REAL
40.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01407
0441 VHz User Volts[5]
Parameters::Motor Control::Fluxing VHz
REAL
50.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01409
0442 VHz User Volts[6]
Parameters::Motor Control::Fluxing VHz
REAL
60.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01411
0443 VHz User Volts[7]
Parameters::Motor Control::Fluxing VHz
REAL
70.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01413
0444 VHz User Volts[8]
Parameters::Motor Control::Fluxing VHz
REAL
80.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01415
0445 VHz User Volts[9]
Parameters::Motor Control::Fluxing VHz
REAL
90.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01417
0446 VHz User Volts[10]
Parameters::Motor Control::Fluxing VHz
REAL
100.0
0.0 to 100.0
%
STOPPED ENGINEER
4
01419
0447 Fixed Boost
Same as PNO 422
REAL
0.0
0.0 to 25.0
%
ALWAYS
TECHNICIAN 6,4
01421
0448 Auto Boost
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 25.0
%
ALWAYS
TECHNICIAN 6,4
01423
0450 Acceleration Boost
Parameters::Motor Control::Fluxing VHz
REAL
0.0
0.0 to 25.0
%
ALWAYS
TECHNICIAN 4
01427
0451 Energy Saving Enable
Parameters::Motor Control::Fluxing VHz
BOOL
FALSE
ALWAYS
TECHNICIAN 4
01429
0453 Vsd Demand
Parameters::Motor Control::Fluxing VHz
REAL
x.x
Min to Max
%
NEVER
TECHNICIAN 4
01433
0454 Vsq Demand
Parameters::Motor Control::Fluxing VHz
REAL
x.x
Min to Max
%
NEVER
TECHNICIAN 4
01435
0455 Rated Motor Current
Setup::Motor Control::Motor Nameplate
Parameters::Motor Control::Motor Nameplate
REAL
1.56
0.00 to 10000.00
A
STOPPED TECHNICIAN 6,4
01437
0456 Base Voltage
Same as PNO 455
REAL
400.00
0.00 to 1000.00
V
STOPPED TECHNICIAN 6,4
01439
0457 Base Frequency
Same as PNO 455
REAL
50.00
0.00 to 1000.00
Hz
STOPPED TECHNICIAN 6,4
01441
0458 Motor Poles
Same as PNO 455
INT
4,
2 to 1000
STOPPED TECHNICIAN 6,4
01443
0459 Nameplate Speed
Same as PNO 455
REAL
1450.00
0.00 to 100000.00
RPM
STOPPED TECHNICIAN 6,4
01445
0460 Motor Power
Same as PNO 455
REAL
0.75
0.00 to 3000.00
kW
STOPPED TECHNICIAN 6,4
01447
0461 Power Factor
Same as PNO 455
REAL
0.71
0.00 to 1.00
STOPPED TECHNICIAN 6,4
01449
0464 100% Speed in RPM
Setup::Motor Control::Control and Type
Parameters::Motor Control::Scale Setpoint
REAL
1500.0
0.0 to 100000.0
RPM
ALWAYS
TECHNICIAN
01455
0465 Speed Demand RPM
Parameters::Motor Control::Scale Setpoint
REAL
x.x
0.0 to 100000.0
RPM
NEVER
TECHNICIAN
01457
0466 Speed Demand Hz
Parameters::Motor Control::Scale Setpoint
REAL
x.x
0.0 to 60000.0
Hz
NEVER
TECHNICIAN
01459
0467 PMAC SVC Auto Values
Parameters::Motor Control::PMAC SVC
BOOL
TRUE
ALWAYS
TECHNICIAN 6,4
01461
0468 PMAC SVC LPF Speed Hz
Parameters::Motor Control::PMAC SVC
REAL
60.00
0.00 to 10000.00
Hz
ALWAYS
TECHNICIAN 6,4
01463
0469 PMAC SVC P Gain
Parameters::Motor Control::PMAC SVC
REAL
2.42
0.00 to 10000.00
ALWAYS
TECHNICIAN 6,4
01465
0470 PMAC SVC I Gain Hz
Parameters::Motor Control::PMAC SVC
REAL
20.00
0.00 to 10000.00
Hz
ALWAYS
TECHNICIAN 6,4
01467
0476 PMAC SVC Open Loop Strt
Parameters::Motor Control::PMAC SVC
BOOL
TRUE
ALWAYS
TECHNICIAN 4
01479
0477 PMAC SVC Start Time
Parameters::Motor Control::PMAC SVC
TIME
0.500
0.000 to 1000.000
s
ALWAYS
TECHNICIAN 4
01481
0478 PMAC SVC Start Cur
Setup::Motor Control::SVC PMAC
Parameters::Motor Control::PMAC SVC
REAL
10.0
0.0 to 600.0
%
ALWAYS
TECHNICIAN 4
01483
0479 PMAC SVC Start Speed
Same as PNO 478
REAL
5
0 to 200
%
ALWAYS
TECHNICIAN 4
01485
0484 Seq Stop Method VHz
Setup::Motor Control::Control and Type
Parameters::Motor Control::Ramp
USINT
(enum)
1
0:DISABLED VOLTAGE
1:RAMP
2:STOP RAMP
3:DC INJECTION
ALWAYS
TECHNICIAN 4
01495
0485 Ramp Type
Parameters::Motor Control::Ramp
USINT
(enum)
0
0:LINEAR
1:S RAMP
ALWAYS
TECHNICIAN
01497
0486 Acceleration Time
Same as PNO 484
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN 6
01499
0487 Deceleration Time
Same as PNO 484
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN 6
01501
0488 Symmetric Mode
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN 6
01503
0489 Symmetric Time
Parameters::Motor Control::Ramp
TIME
10.000
0.000 to 3000.000
s
ALWAYS
TECHNICIAN
01505
0490 Sramp Continuous
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01507
0491 Sramp Acceleration
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s²
ALWAYS
OPERATOR
01509
0492 Sramp Deceleration
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s²
ALWAYS
TECHNICIAN
01511
0493 Sramp Jerk 1
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01513
0494 Sramp Jerk 2
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01515
0495 Sramp Jerk 3
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01517
0496 Sramp Jerk 4
Parameters::Motor Control::Ramp
REAL
10.0
0.0 to 100.0
%/s³
ALWAYS
TECHNICIAN
01519
0497 Ramp Hold
Parameters::Motor Control::Ramp
BOOL
FALSE
ALWAYS
TECHNICIAN
01521
0498 Ramping Active
Parameters::Motor Control::Ramp
BOOL
NEVER
TECHNICIAN
01523
Содержание AC30 series
Страница 4: ...AC30 series Variable Speed Inverter...
Страница 17: ...Product Overview 3 3 AC30 series Variable Speed Inverter Functional Overview Block Diagram for Frames D E F...
Страница 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Страница 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Страница 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Страница 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Страница 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Страница 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Страница 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Страница 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Страница 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Страница 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...
Страница 461: ...AC30 series Variable Speed Inverter...