Fieldbuses
A-25
AC30 series Variable Speed Inverter
Troubleshooting and Tips
The inverter fails to come out of configuration mode
The input or output mapping tables have invalid parameter mappings. The parameter
3130 EtherNet IP State
will report
ERROR
. Check the
parameter
3131 EtherNet IP Diag
to determine which mapping table has the incorrect mapping. Note the input mapping table may only contain
read-writable parameters.
Failure to make a connection
A connection between scanner and the adapter will not be made if:
•
the input and output assembly data sizes of the scanner do not match the input and output mapping data sizes of the inverter
•
the Requested Packet Interval (RPI) of the scanner is set to less than 2ms
Requested Packet Interval (RPI)
When mapping a large amount of data use an RPI of at least 10ms.
Содержание AC30 series
Страница 4: ...AC30 series Variable Speed Inverter...
Страница 17: ...Product Overview 3 3 AC30 series Variable Speed Inverter Functional Overview Block Diagram for Frames D E F...
Страница 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Страница 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Страница 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Страница 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Страница 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Страница 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Страница 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Страница 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Страница 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Страница 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...
Страница 461: ...AC30 series Variable Speed Inverter...