C-4
Parameter Reference
AC30 series Variable Speed Drive
AFE inductance parameter must be set to the value of the total line choke inductance.
AFE VDC Demand parameter sets the required DC link voltage for the common DC link bus. Recommended level for nominal drive voltage rating of
400V (with 820V overvoltage trip level and 410V undervoltage trip level) is 720V.
AFE VDC Min Level parameter defines the level of DC link voltage at which external precharge closure is instigated. By default it is equal to
undervoltage trip level.
For any additional adjustments (if required) the full set of the AFE related parameters can be found in the
Parameters::Regen Control::AFE
menu.
Other (
non-AFE
) drives, supplied through common DC bus
MUST
have the following set-up:
DC Link volts limit feature disabled
If in V/Hz mode the Terminal Voltage Mode parameter set to FIXED
Содержание AC30 series
Страница 4: ...AC30 series Variable Speed Inverter...
Страница 17: ...Product Overview 3 3 AC30 series Variable Speed Inverter Functional Overview Block Diagram for Frames D E F...
Страница 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Страница 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Страница 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Страница 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Страница 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Страница 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Страница 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Страница 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Страница 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Страница 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...
Страница 461: ...AC30 series Variable Speed Inverter...