3-2
Product Overview
AC30 series Variable Speed Inverter
Power Stack Features
General
Switching Frequency
Minimum 2kHz
Default 2kHz (Frames K, L, M & N), 2.5kHz (Frames H & J), 3kHz (Frame G), 4kHz (Frames D, E & F)
Maximum 12kHz (Frames D, E, F & G), 8kHz (Frames H, J, K, L, M & N)
Derating of output current will apply above the default switching frequency.
Output Frequency
Maximum is Switching Frequency divided by 8. This is limited to 590Hz due to export rules.
e.g.
for 4kHz switching frequency it is 4000/8 = 500Hz
Maximum is Switching Frequency divided by 6, in PMAC Motor Closed Loop Control.
If >590Hz is required, please contact your local Parker Sales representative.
Dual Rating
Normal duty (ND)
Heavy duty (HD)
Stack
Protection
Trip Conditions
Output scct: line-to-line & line-to-earth
Overcurrent:
-
Frames D, E, F, G, H, J & K 220% HD current / Stall
-
Frames L, M & N 190% HD current / Stall
Overvoltage & undervoltage
Heatsink over-temperature
Internal over-temperature (Frames J, K, L, M & N only)
Output current imbalance (Frames L, M & N only)
Missing output current sensor (Frames J, K, L, M & N only)
Missing line phase (Frames K, L, M & N only)
Motor Thermistor over-temperature (using GPIO option)
Dynamic Brake scct protection (Frames D, E, F, G, H, J & K only)
Current Limit
Adjustable 110% (ND) or 150% (HD) for 60s
180% shock load limit (Heavy Duty)
Inverse Time
Overload Rating
ND - 110% overload for 60s
HD - 180% overload for 3s (Frames D, E, F, G, H, J & K only), 150% overload for 60s
User
Terminals
Line Input
3 AC input terminals L1, L2, L3 (710 stacks only)
Motor Output
3 AC output terminals - M1, M2, M3 (to be used as line supply connections for AFE applications)
PE
2 protective earth terminals
DC Input
2 DC input terminals DC+ and DC-
Brake Output
2 DC output terminals DB+ and DB to be used when connecting up a Dynamic Brake Resistor
(Frames D, E, F, G, H & J only)
1 DC output terminal DB to be used in conjunction with DC+ when connecting a Dynamic Brake
Resistor (Frame K only)
Содержание AC30 series
Страница 4: ...AC30 series Variable Speed Inverter...
Страница 17: ...Product Overview 3 3 AC30 series Variable Speed Inverter Functional Overview Block Diagram for Frames D E F...
Страница 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Страница 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Страница 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Страница 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Страница 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Страница 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Страница 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Страница 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Страница 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Страница 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...
Страница 461: ...AC30 series Variable Speed Inverter...