C-206
Parameter Reference
AC30 series Variable Speed Drive
Parameter Name
No.
Path
Default
Range
Units
Writable
Speed Loop Pgain
0515
Parameters::Motor Control::Spd Loop
Settings
20.00
0.00 to 3000.00
ALWAYS
Sets the proportional gain of the loop.
Speed error x proportional gain = torque percent.
Speed Loop I Time
0516
Parameters::Motor Control::Spd Loop
Settings
0.100
0.001 to 15.000
s
ALWAYS
This is the integral time constant of the speed loop. A speed error which causes the proportional term to produce a torque demand T,
will cause the integral term to also ramp up to a torque demand T after a time equal to
Speed Loop I Time
.
Speed Loop Int Defeat
0517
Parameters::Motor Control::Spd Loop
Settings
FALSE
ALWAYS
When TRUE, the integral term does not operate.
Speed Loop Int Preset
0518
Parameters::Motor Control::Spd Loop
Settings
0
-600 to 600
ALWAYS
The integral term will be preset to this value when the drive starts.
Spd Loop Dmd Filt TC
0519
Parameters::Motor Control::Spd Loop
Settings
0.0
0.0 to 15.0
ms
ALWAYS
The speed demand is filtered to reduce ripple. The filter is first order with time constant equal to the value of this parameter.
Spd Loop Fbk Filt TC
0520
Parameters::Motor Control::Spd Loop
Settings
1.0
0.0 to 15.0
ms
ALWAYS
The speed feedback is filtered to reduce ripple. The filter is first order with time constant equal to the value of this parameter.
Содержание AC30 series
Страница 4: ...AC30 series Variable Speed Inverter...
Страница 17: ...Product Overview 3 3 AC30 series Variable Speed Inverter Functional Overview Block Diagram for Frames D E F...
Страница 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Страница 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Страница 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Страница 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Страница 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Страница 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Страница 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Страница 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Страница 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Страница 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...
Страница 461: ...AC30 series Variable Speed Inverter...