Trips & Fault Finding
7-13
AC30 series Variable Speed Inverter
Alert message
Possible Cause
Remedy
** ALERT **
APPLICATION LOAD
FAILED
Fault during application download.
Application deleted by the drive
Re-install the application from PDQ or PDD
Custom applications only: check the application for any delays or
loops that may cause the application task to “hang”.
COMMS OPTION
HARDWARE MISMATCH
Parameter 0044 “Comms Required” is not
compatible with the fitted communications
option
Fit the correct communications option.
Change the application to be compatible with the fitted option,
(setting “Comms Required” to NONE will avoid this alert).
COMMS OPTION
CONFIGURATION
ERROR
The configuration settings are not compatible
with the selected option
Refer to the communications option manual, “Troubleshooting”.
IO OPTION
HARDWARE MISMATCH
Parameter 1178 “Option IO Required” is not
compatible with the fitted IO option
Fit the correct IO option.
Change the application to be compatible with the fitted option,
(setting “Option IO Required” to NONE will avoid this alert).
** ALERT **
FEEDBACK MISSING
Attempt to run in Encoder Feedback control
mode with no feedback device fitted, (or
configured).
Change the control mode to VHz or Sensorless
Fit the correct feedback option
Check parameter 1178 “Option IO Required”
** ALERT **
IO OPTION CHANGED
The IO Option has been changed.
IO Option removed, IO Option attached or different IO Option
fitted.
This alert is for information only and occurs just once following the
change.
** ALERT **
COMMS OPTION
CHANGED
The Communications Option has been
changed.
Comms Option removed, Comms Option attached or different
Comms Option fitted.
This alert is for information only and occurs just once following the
change.
** ALERT **
UPDATING LANGUAGE
Updating the translations held in the GKP. This
may happen the first time a language is
selected.
No action required. The language update should complete within
one minute.
PCR NOT CLOSED
The pre-charge relay is not closed, (probably
due to low DC Link volts)
Check the 3-phase input or common supply.
SYSTEM BOARD
HARDWARE MISMATCH
Parameter 1739 “System Board Required” not
correctly set.
This indicates that the drive has never been commissioned. It is
advised to reset all parameters to their default values.
** ALERT **
SYSTEM BOARD
CHANGED
Unreliable connection to the system board
Power off / on then verify that the system board is functioning
correctly.
If this message occurs more than once contact the service
department for assistance.
Содержание AC30 series
Страница 4: ...AC30 series Variable Speed Inverter...
Страница 17: ...Product Overview 3 3 AC30 series Variable Speed Inverter Functional Overview Block Diagram for Frames D E F...
Страница 18: ...3 4 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames G H J...
Страница 19: ...Product Overview 3 5 AC30 series Variable Speed Inverter Block Diagram for Frame K...
Страница 20: ...3 6 Product Overview AC30 series Variable Speed Inverter Block Diagram for Frames L N...
Страница 22: ...3 8 Product Overview AC30 series Variable Speed Inverter...
Страница 65: ...6 27 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Scoping Drive Parameters...
Страница 66: ...6 28 Setup Wizard AC30 series Variable Speed Inverter...
Страница 84: ...7 18 Trips Fault Finding AC30 series Variable Speed Inverter...
Страница 122: ...9 6 Fire Mode AC30 series Variable Speed Drive...
Страница 188: ...C 6 Parameter Reference AC30 series Variable Speed Drive...
Страница 189: ...Parameter Reference C 7 AC30 series Variable Speed Drive...
Страница 461: ...AC30 series Variable Speed Inverter...