890GTR Inverter Power Manual HA502996
WARNING
:
IMPORTANT
All electrical work must be done in accordance with local, national, and/or international electrical codes by a qualified
electrician.
IMPORTANT
WARNING: Battery Strings can produce dangerous electrical voltage levels.
IMPORTANT
WARNING: Extreme Arc Flash and Shock Hazards
Flash Hazard Boundary 60”
Up to 24.46 Cal/cm
2
at 18”
Class 3 PPE Level (Rated at 25 Cal/cm
2
) – 2 layers of clothing: cotton und fire resistant shirt and
pants or cov multilayer flash suit, VR gloves-tools, with appropriate flash hood.
Limited Approach Boundary 120”
Restricted Approach Boundary 12”
Prohibited Approach Boundary 1”
This section does not take the place of the specific training supervisors must provide their workers who use personal protective
equipment (PPE)
Refer to the most current revision of the OSHA informational booklet OSHA 3151-12R for information on personal protective
equipment (PPE).