C-7
Compliance
890GTR Inverter Power Manual HA502996
EMC
Emissions Limits
Conducted
Frequency (MHz)
DB (
µ
V)
Product Specific
Quasi Peak
Average
EN 61800-3
where I ≤100A
0.15 - 0.5
0.5 - 5.0
5.0 - 30.0
decreasing with log of frequency to:
100
86
90
70
90
76
80
60
Category C3
Table 17
where I ≥100A
0.15 - 0.5
0.5 - 5.0
5.0 - 30.0
130
125
115
120
115
105
Where these levels are too high and to ensure compatibility with other equipment, EMC filters are available from Parker.
Radiated
Frequency (MHz)
DB (
µ
V)
Product Specific
Quasi Peak
EN 61800-3
30≤ f- ≤230
230≤ f- ≤1000
50
60
Category C3
(Table 18)
Measured at 10m
Where these levels are too high and to ensure compatibility with other equipment, Parker can advise on suitable counter-measures.