Technical Specifications
E-15
890GTR Inverter Power Manual HA502996
Changing Voltage and Frequency Fault Trip Levels and
Times
WARNING: Only trained personnel should attempt to adjust grid fault response characteristics. Incorrect
settings may result in personnel hazards due to prolonged energized island conditions caused by the 890GTR
inverter.
WARNING: Do not attempt to adjust the fault levels or trip times while the inverter is operating.
Adjustments to the Voltage and Frequency Fault Tip Levels and Times can be made through the DSE Lite tool that is
included with the shipping memory stick, is installed on the equipped touchscreen, and is available through download from
our website or by contacting Parker EGT customer service.
To access the 890GTR configuration, first ensure the inverter is not synchronized to the Grid and that the AC and DC
main power disconnect devices are in the open state. Open DSE Lite on your computer in Wizard mode. Consult the
factory on how to get access to Wizard mode functionality. Next connect to the inverter through the DSE tool which can
be accomplished 1 of 2 ways.