Safety
1-5
Safety Information
890GTR Inverter Power Manual HA502996
Hazards
DANGER! – Ignoring the following may result in injury
1.
This equipment can endanger life by exposure to high
voltages.
2.
The equipment must be permanently earthed due to the high
earth leakage current, and the supplies and loads must be
connected to an appropriate safety earth.
3.
Ensure all incoming supplies are isolated before working on
the equipment. Be aware that there may be more than one
supply connection to the inverter.
4.
There may still be dangerous voltages present at power
terminals (battery inputs and DC bus) when the inverter is
stopped.
5.
For measurements use only a meter to IEC 61010 (CAT III or
higher). Always begin using the highest range. CAT I and CAT II
meters must not be used on this product.
6.
Under normal circumstances the AC and DC Bus should
discharge within 10 minutes. Use a meter capable of measuring
up to 1000 VDC & 600 VAC RMS to confirm that less than 50V is
present on the DC BUS and between all power terminals and
earth before working on or near the DC Bus.
7.
Unless otherwise stated, this product must NOT be dismantled. In
the event of a fault the component must be returned.
Содержание 890GTR
Страница 2: ......
Страница 38: ...3 10 Installation 890GTR Inverter Power Manual HA502996 Lifting Dimensions All dimensions in mm BOTTOM ...
Страница 90: ...8 1 Ethernet 890GTR Inverter Power Manual HA502996 Chapter 8 Ethernet ...
Страница 109: ...Compliance C 10 890GTR Inverter Power Manual HA502996 ...
Страница 113: ...Compliance C 14 890GTR Inverter Power Manual HA502996 ...
Страница 130: ...E 12 Technical Specifications 890GTR Inverter Power Manual HA502996 Earthing Safety Details ...