Trips & Fault Finding
5-3
890GTR Inverter Power Manual HA502996
Resetting a Trip Condition
Before a trip can be reset, the trip condition must be removed.
Note
A Heatsink Over-temperature trip may not reset immediately. The unit needs time to cool sufficiently.
Using Modbus TCP
To reset a trip in Remote Mode:
Remove the trip condition
Set Reset Fault bit True, and then return bit to False.
More than one trip can be active at any time. For example, it is possible for both the HEATSINK and the OVERVOLTAGE trips to be
active. Alternatively it is possible for the inverter to trip due to an OVERCURRENT error and then for the HEATSINK trip to become
active after the inverter has stopped (this may occur due to the thermal time constant of the heat sink).