![Parker 890GTR Скачать руководство пользователя страница 146](http://html1.mh-extra.com/html/parker/890gtr/890gtr_product-manual_756103146.webp)
E-28
Technical Specifications
890GTR Inverter Power Manual HA502996
Connector Torque Requirements
Bolt Size
Torque (NM)
Steel 6/6
Steel 8/8
Steel 4/6
Brass 20T UTS
Installation Inspection Installation Inspection Installation Inspection Installation Inspection
M4
1.9
1.69
3.5
3.0
1.3
1.1
1.8
1.5
8-32
2.2
1.9
3.8
3.2
1.5
1.3
-
-
10-32
3.2
2.7
5.4
4.6
2.1
1.8
-
-
M5
4.0
3.4
7.1
6.0
2.7
2.3
3.6
3.1
M6
6.8
5.8
11.5
9.7
4.5
3.8
5.4
4.6
1/4-20
7.6
6.5
13.0
11.1
5.1
4.3
-
-
5/16-18
15.7
13.3
26.7
22.7
10.4
8.8
-
-
M8
16.5
14.0
28.0
24.3
11.0
9.4
12.3
10.4
3/8-18
27.9
23.7
47.5
40.4
18.6
15.8
-
-
M10
32.8
27.9
55.0
47.5
21.8
18.5
23.7
20.2
M12
91.0
77.4
155.1
130.2
60.6
51.5
66.0
56.1
1/2-12
68.0
57.8
115.8
98.4
45.3
38.5
-
-
M16
142.0
120.7
241.0
208.8
95.0
80.8
101.0
85.9
M20
277.0
235.5
465.1
396.0
185.0
157.3
205.0
174.3
Use the above torques for 6/6 screws for all busbar connections and general use unless the screw material requires lower torque.
Use the torques for 8/8 screws only where specified (These torques are generally used for very high loads).
Содержание 890GTR
Страница 2: ......
Страница 38: ...3 10 Installation 890GTR Inverter Power Manual HA502996 Lifting Dimensions All dimensions in mm BOTTOM ...
Страница 90: ...8 1 Ethernet 890GTR Inverter Power Manual HA502996 Chapter 8 Ethernet ...
Страница 109: ...Compliance C 10 890GTR Inverter Power Manual HA502996 ...
Страница 113: ...Compliance C 14 890GTR Inverter Power Manual HA502996 ...
Страница 130: ...E 12 Technical Specifications 890GTR Inverter Power Manual HA502996 Earthing Safety Details ...