Compliance
C-12
890GTR Inverter Power Manual HA502996
EMC General Installation Considerations
Earthing Requirements
IMPORTANT
Protective earthing always takes precedence over EMC screening.
Protective Earth (PE) Connections
Note
In accordance with installations to EN60204, only one protective earth conductor is permitted at each protective earth
terminal contacting point.
Local wiring regulations take precedence and may require the protective earth connection of the transformer to be connected locally,
i.e. not as specified in these instructions. This will not cause shielding problems because of the relatively high RF impedance of the
local earth connection.
EMC Earth Connections
For compliance with EMC requirements, we recommend that the “0V/signal ground” be separately earthed. When a number of units
are used in a system, these terminals should be connected together at a single, local earthing point.
Control and signal cables for the encoder, all analogue inputs, and communications require screening with the screen connected only
at the inverter end. However, if high frequency noise is still a problem, earth the screen at the non-VSD end via a 0.1
µ
F capacitor.
Note
Connect the screen (at the VSD end) to the VSD protective earth point, and not to the control board terminals.
Cabling Requirements
Planning Cable Runs
•
Use the shortest possible grid cable lengths.
•
Keep electrically noisy and sensitive cables apart.
•
Keep electrically noisy and sensitive parallel cable runs to a minimum. Separate parallel cable runs by at least 0.25 metres.
For runs longer than 10 metres, separation should be increased proportionally. For example if the parallel runs were 50m,
then the separation would be (50/10) x 0.25m = 1.25m.
•
Sensitive cables should cross noisy cables at 90
°
.
•
Never run sensitive cables close or parallel to the grid or dc link conductors for any distance.
Содержание 890GTR
Страница 2: ......
Страница 38: ...3 10 Installation 890GTR Inverter Power Manual HA502996 Lifting Dimensions All dimensions in mm BOTTOM ...
Страница 90: ...8 1 Ethernet 890GTR Inverter Power Manual HA502996 Chapter 8 Ethernet ...
Страница 109: ...Compliance C 10 890GTR Inverter Power Manual HA502996 ...
Страница 113: ...Compliance C 14 890GTR Inverter Power Manual HA502996 ...
Страница 130: ...E 12 Technical Specifications 890GTR Inverter Power Manual HA502996 Earthing Safety Details ...