The 6911 Keypad
Notes:
1.
The first sample is taken at the point of the logging start condition.
2.
A power interruption during the logging process results in the text “Power interruption may have
affected Data Log” being added to the log file when power is resumed. The total number of log
events, if in use, is not corrected for the down-time. A power interruption that occurs when a time
trigger is set up will halt data logging.
3.
Any change to the filename, trigger, or sample interval will halt data logging.
4.
The file browser can be used during data logging.
5.
Excessive MMI or memory card activity can delay data sample times if the interval is set very short.
F4 : NEXT MENU
Press this key to display next Multi-Key menu set.