PARAGON 2000 Plus 

Installation Instructions

 

 

SECTION EIGHT 

Fireplace Requirements Continued 

 
CLEARANCE TO SHELF 

Minimum  clearance  from  hearth  to  underside  of  combustible  shelf  should  be  700mm 
provided  shelf  depth  150mm  or  less.  This  height  may  be  reduced  to  640mm  for  a  shelf 
depth of 100mm or less 

 

When  the  shelf  depth  is  increased  by  increments  of  12.5  mm  greater  than  150mm,  add 
25mm to the 700mm minimum clearance. 
 

CLEARANCE TO SIDES OF FIRE 

Minimum  width  between  vertical  sides  of  combustible  surround  should  not  be  less  than 
700mm  provided  fire  is  central  to  surround  and  sides  do  not  project  more  than  150 mm.  
When vertical side forward projection is increased by 12.5 mm add 50 mm to inside width 
of surround. 

 

N.B.  When fire is fitted this provides a minimum side clearance of 100mm. 
 
Care should be taken to prevent any damage being caused to surrounding soft furnishings 
or decoration, e.g. many embossed vinyl wall coverings may become discoloured if placed 
too close to the appliance. 
 

VENTILATION 

 
In  the 

United  Kingdom

  no  special  ventilation  bricks  or  vents  are  required  into  the  room 

containing  the  appliance,  provided  normal  adventitious  room  ventilation  exists.  The 
installer must satisfy this point by carrying out a mandatory spillage test. 
 
In the 

Republic of Ireland

 permanent ventilation must comply with the rules in force 

 

SECTION NINE 

To Install the Appliance 

 
EXAMINE FLUE / CHIMNEY

 

Check that  the flue/chimney conforms to the required specifications as previously stated.  
Examine the condition and carry out any remedial work.  If the flue/chimney has been used 
for solid fuel or oil, it should be swept prior to appliance installation. A smoke test must be 
carried  out  to  check  that  satisfactory  smoke  clearance  has  been  established.    If  all  the 
smoke is not drawn into the flue, pre-heat the flue with a blowtorch or similar and re-check.  
If there is any uncertainty examine for the cause and, if necessary, seek expert advice. 
 

CONNECTING THE GAS SUPPLY 

Determine where the gas supply is to be connected to the appliance.  This may be done 
from  the  front  of  the  unit  from  either  the  left  or  right  side,  or  a  concealed  fitting  from  the 
rear. 
 
 
 

Содержание 2000 Plus Xtra

Страница 1: ...SER INSTALLATION MAINTENANCE INSTRUCTIONS Please read these instructions carefully before you start using the appliance Keep this booklet handy for future reference This appliance is for use in GREAT...

Страница 2: ...ireplace Requirements 13 Hole in the Wall installations 14 Clearance to Shelf 15 Clearance to Side of Fire 15 Ventilation 15 SECTION NINE To Install the Appliance 15 Examine Flue Chimney 15 Connecting...

Страница 3: ...s and eye protection After handling wash hands and other exposed parts If a vacuum is used for cleaning the fuel bed or cleaning after servicing installation it is recommended that it be of the type f...

Страница 4: ...be checked prior to contacting a service engineer SECTION TWO Operation The pilot can be left on or the pilot can be extinguished and relit each time the fire is used The appliance Control Knob is pos...

Страница 5: ...sits A vacuum cleaner may only be used after the loose components and moulded shapes have been removed CARE SHOULD BE TAKEN TO AVOID CONTACT WITH THE REFRACTORY LINING THIS IS A DELICATE SURFACE AND S...

Страница 6: ...de front support over front edge of fire where the left right front coals meet see below Note the loose coal provided consist of 5 off shaped as coal A 9 off shaped as coal B Separate the coal into th...

Страница 7: ...PARAGON 2000 Plus Users Instructions SECTION THREE Fuel Bed Cleaning and Layout Cont Lay second row of loose coals 3 off B and 2 off A shapes as shown Lay third row of loose coals 2 off B shape and 1...

Страница 8: ...Total 12 PEBBLE LAYOUT WARNING Take great care when positioning the pebbles to avoid marking the black linings Ensure the BASE MATRIX is in position as shown located against the rear edge of the burn...

Страница 9: ...ARAGON 2000 Plus Users Instructions SECTION THREE Fuel Bed Cleaning and Layout Cont Lay one row of pebbles at the front of the fire as shown Lay another row of loose pebbles shown Lay another row of l...

Страница 10: ...re purpose built ventilation but if for any special reason purpose built ventilation is provided it should be checked periodically to ensure freedom from obstruction Ventilation in the Republic of Ire...

Страница 11: ...ernment s Standard Assessment Procedure SAP for energy rating of dwellings SECTION SIX Regulations and Warnings THIS APPLIANCE MUST ONLY BE INSTALLED IN THE GB OR IRELAND Only to be used in sufficient...

Страница 12: ...t The Building Standards Scotland Consolidation Regulations issued by the Scottish Development Office SECTION SEVEN Siting the Appliance The fire can be installed in the following flues and locations...

Страница 13: ...fitted when the appliance is installed in this type of flue Note A brick or stone chimney with a 125 mm 5 ins minimum diameter flue liner conforming to BS 715 may be used Provided a suitable sealing p...

Страница 14: ...tion should be given to the location of the appliance ensuring it is very visible and it should be positioned at a height were it can clearly be seen on approach Frets and Fascias used for HOLE in the...

Страница 15: ...ed too close to the appliance VENTILATION In the United Kingdom no special ventilation bricks or vents are required into the room containing the appliance provided normal adventitious room ventilation...

Страница 16: ...tated to the required position A suitable isolating cock should always be fitted in the supply feed to the fire to facilitate servicing FIXING FIRE INTO OPENING Remove the paper backing from the lengt...

Страница 17: ...nt on the inlet elbow and fit pressure gauge Turn on gas the appliance Purge the air from the appliance by rotating the control to the ignition position push in to allow the air in the pipework to be...

Страница 18: ...The curing effect of heating the fuel bed and other Refractory components will cause an initial odour This is due to the starch used in the manufacturing process and is non toxic Any debris should be...

Страница 19: ...se fuel bed components 4 Lift away carefully both Left hand and right hand front matrix 5 Lift away carefully rear matrix 6 Remove plastic knob from gas control tap 7 Undo and remove four screws from...

Страница 20: ...e REPLACEMENT OF OXY PILOT ASSEMBLY NOTE If the pilot assembly is replaced it must be replaced by an identical unit from the same manufacturer and replaced as a complete unit 1 Repeat operations 1 11...

Страница 21: ...ust be installed by a GAS SAFE registered person 2 The appliance must be used in accordance with the users instructions 3 The appliance must be serviced annually by a GAS SAFE registered person 4 The...

Страница 22: ...ontact the helpdesk Model 2000 Plus Serial No This information can be found on the label attached to the packaging and on the data badge which is located on the appliance flange top right behind trim...

Страница 23: ...irst annual service Engineer Name Gas Safe Registration No Date of Second annual service Engineer Name Gas Safe Registration No Date of Third annual service Engineer Name Gas Safe Registration No Date...

Страница 24: ...LT5048 Iss 9 11 12 24...

Страница 25: ...YOUR DETAILS Name ________________________________ Address ________________________________ Post Code TELEPHONE No PRODUCT DETAILS Model 2000 Plus Serial No Date of Purchase This information can be fo...

Страница 26: ...LT5048 Iss 9 11 12 26...

Страница 27: ...LT5048 Iss 9 11 12 27...

Страница 28: ...ox Assembly Burner Tray Box Assembly Ceramics Set Part no 5568 Ceramics Set Part no 4989 Fixing kit 0705 includes 4 magnets foam seal Fixing kit 0705 includes 4 magnets foam seal Foam Sealing Strip Fo...

Отзывы: