LT5048 (Iss 9: 11/12)
12
ALL DIMENSIONS IN mm
PRE-CAST FLUE BLOCK
ADDITIONAL DEPTH INCLUDING PLASTER AND FIREPLACE
"A"
300
NONE
SPA
CE
R
20mm
30mm
94
80
74
60
64
50
"A"
"X"
380mm - 435mm
37
47
67
320
310
"X" MINIMUM (INCLUDING PLASTER)
0
7
21
43mm
"A"
215 OR 185 MIN. IF FLUE AS NEVER BEEN
USED FOR SOLID FUEL
700 MIN.
WHEN "A"= 150
680 MIN.
552 MIN.- 578 MAX.
300 MIN.
50 MIN.
ALL DIMENSIONS IN mm
380 MIN.-435 MAX.
PARAGON 2000 Plus
Installation Instructions
SECTION SIX
Regulations and Warnings Continued
A non-combustible hearth must be provided to comply with the building regulations or a
suitable proprietary fire surround with a 100 degrees C rating.
During initial firing an odour may be evident. This is the binder used during the
manufacture of the fibre components and there are no harmful effects produced
.
The following are the relevant Codes of Practice and British Standards: -
BS 5871
BS 8303
BS 5440 part 1
BS 1251
BS 6891
BS 6461 parts 1 & 2
BS 715
BS 1289pt 1& 2
Note:- This appliance must be installed to current versions of the above standards
and include any relevant amendments.
The Building Regulations issued by the Department of the Environment
The Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish
Development Office.
SECTION SEVEN
Siting the Appliance
The fire can be installed in the following flues and locations: -
CLASS ONE
A conventional brick or stone chimney as used for a solid fuel appliance with a typical
effective cross-sectional dimension of 225 x 225 mm (9 x 9 ins) or a lined flue with a
minimum diameter of 125 mm (5 ins)
Note: The restrictor plate, which is separately packed, may be fitted to flue of
175mm (7") or greater. This being subject to satisfactory product clearance
.
Fireplace opening must be 552 mm - 578 mm high by 380 mm
– 435 mm wide (or up to
458 mm if the cable fixing system is used).
The opening depth must be a minimum of 215 mm to allow sufficient volume for debris
collection (this depth may be reduced to 185 mm if the chimney is new or has never been
used for solid fuel or oil before). To obtain this depth it may be necessary to remove the
chairbrick.
Note: spacers are available in 20mm and 42mm to further reduce the
opening depth if required (if a spacer is used then the thickness of the spacer must
be added to the minimum 300mm hearth depth to comply with regulations.
Any permanent flue restriction or variable dampers are to be removed or locked fully open.
The chimney should be swept prior to installation if not new.