LT5048 (Iss 9: 11/12)
14
PARAGON 2000 Plus
Installation Instructions
SECTION EIGHT
Fireplace Requirements Continued
Hole in the Wall Installation
Please read these instructions carefully if you intend an Installation
without a hearth.
This appliance must be installed in accordance with all relevant sections of
approved document “J” of the building regulations
It is recommended that a non combustible hearth extends a minimum of 300mm forward of
the fire opening and a minimum of 150mm either side, and that a rise exist at the front
edge and sides of the hearth of a minimum of 50mm.
The fire may be installed so that its base sits on a surface of a fire opening at least 105
mm up from the floor
(this is to ensure that no flame or incandescent material is less than
225mm above the floor,
a requirement of approved document “J”)
. Where this is the case
a means must be provided to support the fret this may typically be meet with a small
projecting hearth of minimum 100mm.Unless the fret is fixed to the appliance or is an
integral part of the fascia of the appliance.
Consideration should be given to the location of the appliance ensuring it is very visible
and it should be positioned at a height were it can clearly be seen on approach.
Frets, and Fascias used for HOLE in the WALL must be compliant with Paragon Fires CE
approval; these are listed at the end of this page.
Where the fire is fitted as a “Hole in the Wall” without a hearth the installer MUST ensure
the appliance is fixed firmly into the opening to ensure no movement takes place to the
fuel bed when the appliance controls are operated.
The installer MUST ensure that the fuel bed is laid correctly and securely
The installer MUST advise the user that care should be taken when the appliance is in use
to ensure occupants
do not
get unnecessarily close to the appliance or position furniture
or other appliances to close.
The installer MUST remind user of the requirement to fit a “secure fireguard” where the
room is used by elderly, infirm or young persons.
The installer MUST explain to the user that the area immediately in front of the appliance
must always be keep clear of combustible items other than the floor covering (which must
be fixed)
HOLE in the WALL installations
List of approved Paragon Frets
Wellington 2000
Gate
Post
List of Approved Fascias
Odyssey 2001
Solar
The Box