5 - 50
3. Remote Controller Servicing Functions
5
VRF SYSTEMS Indoor Unit
CZ-RTC2
Fig. 3-6
Test Run Function
Operates the unit with the thermostat forced ON.
<Procedure of CZ-RTC2>
1
Press and hold the
button for 4 seconds or
longer.
2
“TEST” appears on the remote controller LCD
display (Fig. 3-6).
3
Start operation.
4
Press the
button to return to normal remote
controller display.
<Pr
1
Keep pressing the
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select "4. Test run" on the LCD display and press
the
button.
Change the display from OFF to ON by pressing
the
or
button. Then press the
button.
Fig. 3-7
3
Press the
button. “TEST” will be displayed
on the LCD display.
4
Press the
button. Test run will be started.
Test run setting mode screen appears on the LCD
display.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
[
] Confirm
Test run
Change
20:30 (THU)
Test run
ON
CZ-RTC3 / CZ-RTC5A
TEST
START
[ ]
20:30 (THU)
TEST
20:30 (THU)
COOL
MODE
SM830231-00̲Single̲欧州.indb 19
2014/04/04 13:48:34
START
[ ]
20:30 (THU)
ocedure of CZ-RTC3 / CZ-RTC5A>
<Procedure of CZ-RTC4>
Fig. 3-8
1 Press and hold the
button for 4 seconds or
longer.
2 “
” appears on the remote controller LCD
display (Fig. 3-8).
3 Press the
button to start the test run.
The outdoor unit will not operate for
approximately 3 minutes after the power
is turned ON and after operation is stopped.
4 Press the button to return to normal remote controller display.
•
The temperature cannot be adjusted in Test Run mode.
(This mode places a heavy load on the machines.
Therefore use it only when performing the test run.)
•
The test run can be performed using the HEAT, COOL,
or FAN operation modes.
•
To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after
60 minutes.
•
The operation is possible even if the cassette-type ceiling panel has not been installed.
(“P09” display does not occur.)
•
If correct operation is not possible, an error code is
displayed on the remote controller LCD display.
A
°
°
3
4
1
2
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 50
17/03/08 18:34:08
Содержание S-22MF2E5A8
Страница 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Страница 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Страница 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Страница 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Страница 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Страница 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Страница 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Страница 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...