5 - 2
1. Simple Settings Function
5
VRF SYSTEMS Indoor Unit
•
This allows the filter lifetime, operating mode
priority change, central control address, and other
settings to be made for an individual or group-
control indoor unit to which the remote controller
used for simple settings is connected.
When simple settings mode is engaged, operation
stops at the individual or group-control indoor unit
to which the remote controller for simple settings is
connected.
<Procedure of CZ-RTC2>
À
Press and hold the
and
buttons
simultaneously for 4 seconds or longer.
Á
“
,” unit No. “
” (or “
” in the case of
group control), item code “
,” and settings data
“
” are displayed blinking on the remote
controller LCD display (Fig. 1-1). At this time, the
indoor unit fan (or all indoor unit fans in the case of
group control) begins operating.
Â
If group control is in effect, press the
button and select the address (unit No.) of the
indoor unit to set. At this time, the fan at the indoor
unit begins operating.
* If unit No. “
” is displayed, the same setting
will be made for all indoor units.
Ã
Press the temperature setting
/
buttons to select the item code to change.
Ä
Press the timer time
/
buttons to select the
desired setting data.
* For item codes and setting data, refer to the
following page.
Å
Press the
button. (The display stops blinking
and remains lit, and setting is completed.)
Æ
Press the
button to return to normal remote
controller display.
Fig. 1-1
3
4
1
6
5
7
2
[Remote Controller Functions Section]
<Procedure of CZ-RTC3 / CZ-RTC5A>
Fig. 1-2
1
Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “7. Simple settings” on the LCD display and
press the
button.
The “Simple settings” screen appears on the LCD
display.
Select the “Unit no.” by pressing the
or
button for changes.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
[
] Confirm
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Simple settings
Unit no.
Code no.
Set data
01
3-1
0001
Sel.
Next
20:30 (THU)
3
Select the “Code no.” by pressing the
or
button.
Change the “Code no.” by pressing the
or
button.
4
Select the “Set data” by pressing the
or
button.
Select one of the “Set data” by pressing the
or
button.
Then press the
button.
5
Select the “Unit no.” by pressing the
or
button and press the
button.
The “Exit simple settings and restart?” (Simple
setting-end) screen appears on the LCD display.
Select “YES” and press the
button.
Simple settings
Unit no.
Code no.
Set data
1
0
0
0
1
-
3
Sel.
Next
20:30 (THU)
01
Simple settings
Unit no.
Code no.
Set data
3-1
Sel.
20:30 (THU)
01
0002
Simple settings
Unit no.
Code no.
Set data
ALL
Sel.
Next
20:30 (THU)
01
0002
Exit simple settings
and restart?
NO
YES
SM830231-00̲Single̲欧州.indb 3
2014/04/04 13:48:31
START
[ ]
20:30 (THU)
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 2
17/03/08 18:33:40
Содержание S-22MF2E5A8
Страница 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Страница 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Страница 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Страница 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Страница 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Страница 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Страница 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Страница 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...