5 - 24
2. Detailed Settings Function
5
VRF SYSTEMS Indoor Unit
3. Detailed Settings Function
1 Keep pressing the
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
3
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “8. Detailed settings” on the LCD display
and press the
button.
The “Detailed settings” screen appears on the
LCD display.
Select the “Unit no.” by pressing the
or
button for changes.
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Detailed settings
Unit no.
Code no.
Set data
10
1-1
0001
Sel.
Next
20:30 (THU)
4 Select the “Code no.” by pressing the
or
button.
Change the “Code no.” to “5D” by pressing the
or
button (or keeping it pressed).
Detailed settings
Unit no.
Code no.
Set data
1
0
0
0
1
-
1
Sel.
Next
20:30 (THU)
5D
5 Select the “Set data” by pressing the
or
button.
Select one of the “Set data” in “Table for DC Fan
Motor Tap Setting (Table 2-1 – Table 2-3)” by
or
button.
Then press the
button.
6
Detailed settings
Unit no.
Code no.
Set data
1-1
Sel.
20:30 (THU)
5D
0003
[
] Confirm
Press the
The “Exit detailed settings and restart?” (Detailed
setting-end) screen appears on the LCD display.
Select “YES” and press the
button.
Detailed settings
Unit no.
Code no.
Set data
ALL
Sel.
Next
20:30 (THU)
01
0002
Exit detailed settings
and restart?
NO
YES
button.
If you wish to change the selected indoor unit,
follow the step .
2
<Procedure of CZ-RTC3 / CZ-RTC5A>
Stop the system before performing these steps.
pressing the
<Procedure of CZ-RTC4>
* Failure to make this setting may result in
decreased airflow and condensation.
Stop the system before performing these steps.
1 Press and hold the
,
and
b
uttons
simultaneously for 4 seconds or longer.
2 If group control is in effect, press the
button
to set. At this time, the fan at the indoor unit begins
and select the address (unit No.) of the indoor unit
operating.
3 Designate the item code
by adjusting the
Temperature Setting
/
buttons.
4 Press the timer time
/
buttons to select the
desired setting data.
*
For item codes and setting data, see
Table 2-1 – Table 2-3.
5 Press the
button.
(The display stops blinking and remains lit, and
setting is completed.)
If you wish to change the selected indoor unit,
follow the step
2
.
6 Press the
button to return to normal remote
controller display.
1
5
6
2
2
4
3
4
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 24
17/03/08 18:33:49
Содержание S-22MF2E5A8
Страница 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Страница 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Страница 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Страница 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Страница 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Страница 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Страница 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Страница 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...