VRF SYSTEMS Indoor Unit
VRF SYSTEMS Indoor Unit
2.Auto address setting
<Procedure of CZ-RTC3 / CZ-RTC5A>
1
Keep pressing the
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “9. Auto address” on the LCD display and
press the
button.
3
The “Auto address” screen appears on the LCD
display.
Change the “Code no.” to “A1” by pressing the
or
button.
4
Select the “O/D unit no.” by pressing the
or
button.
Select one of the “O/D unit no.” for automatic
address by pressing the
or
button.
Then press the
button.
Approximately about 10 minutes are required.
When automatic address setting is completed, the
units return to normal stopped status.
1
Keep pressing the
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “7. Simple settings” on the LCD display and
press the
button.
The “Simple settings” screen appears on the LCD
display.
Select the “Unit no.” by pressing the
or
button for changes.
The indoor unit fan operates only at the selected
indoor unit.
7-2. Auto address setting
Checking indoor unit addresses
Fig. 2
Maintenance func
10. Set elec. consumption
12. Check touch key
Sel.
Page [
] Confirm
20:30 (THU)
11. Set touch key
9. Auto address
Auto address
Code no.
O/D unit no.
Sel.
Next
20:30 (THU)
1
A1
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Simple settings
Unit no.
Code no.
Set data
01
3-1
0001
Sel.
Next
20:30 (THU)
SM830231-00̲Single̲欧州.indb 22
2014/04/04 13:48:35
START
[ ]
20:30 (THU)
Test Run
1
2
3
4
5
6
7
8
9
2. Auto Address Setting
<Procedure of CZ-RTC4>
1
2
3
4
4
Checking indoor unit addresses
<If 1 indoor unit is connected to 1 remote controller>
1. Press and hold the
button and
button for 4
seconds or longer (simple settings mode).
2. The address is displayed for the indoor unit that is
connected to the remote controller.
(Only the address of the indoor unit that is connected
to the remote controller can be checked.)
3. Press the
button again to return to normal remote
controller mode.
<If multiple indoor units are connected to 1 remote
controller (group control)>
1.
button and
button for 4
seconds or longer (simple settings mode).
2.
Press and hold the
“ALL” is displayed on the remote controller.
3. Next, press the
button.
4. The address is displayed for 1 of the indoor units which is
connected to the remote controller. Check that the fan of
that indoor unit starts and that air is discharged.
5. Press the
button again and check the address of
each indoor unit in sequence.
6. Press the
again to return to normal remote controller
mode.
Number changes to
indicate which indoor
unit is currently
selected.
Indoor unit address
Selecting each refrigerant system individually for
automatic address setting
Automatic address setting for each system
: Item code “A1”
1. Press the remote controller timer time
button and
button at the same time.
(Press and hold for 4 seconds or longer.)
2. Next, press either the temperature setting
button. (Check that the item code is “A1.”)
3. Use either the
or
button to set the system
No. to perform automatic address setting.
4. Then press the
button.
(Automatic address setting for one refrigerant system
begins.) (When automatic address setting for one
system is completed, the system returns to normal
stopped status.)
<Approximately 4 – 5 minutes is required.>
” is
(During automatic address setting, “
displayed on the remote controller.
This message disappears when automatic address
setting is completed.)
5. Repeat the same steps to perform automatic address
setting for each successive system.
*
Automatic address setting in Cooling mode cannot be
done from the remote controller.
NOTE
/
After automatic address setting has been completed,
be sure to record them for future reference.
List the outdoor main unit system address and the
addresses of the indoor units in that system in an easily
visible location (next to the nameplate), using a
permanent marking pen or similar means that cannot
be abraded easily.
Example:
These numbers are necessary for later maintenance.
Please be sure to indicate them.
(Outdoor) 1 - (Indoor) 1-1, 1-2, 1-3…
(Outdoor) 2 - (Indoor) 2-1, 2-2, 2-3…
Request concerning recording the
indoor/outdoor unit combination Nos.
Number changes to
indicate which indoor
unit is currently
selected.
Indoor unit address
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 5
2017/02/01 14:10:32
Содержание S-22MF2E5A8
Страница 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Страница 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Страница 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Страница 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Страница 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Страница 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Страница 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Страница 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...