2. Detailed Settings Function
5
VRF SYSTEMS Indoor Unit
Item code
Item
Setting data
No.
Description
(1B)
Forced thermostat ON time
0000
5 minutes
0001
4 minutes
Cooling discharge
temperature shift
–010
Shifts discharge temperature setting 10°C down
–009
Shifts discharge temperature setting 9°C down
–008
Shifts discharge temperature setting 8°C down
0010
Shifts discharge temperature setting 10°C up
Heating discharge
temperature shift
–010
Shifts discharge temperature setting 10°C down
–009
Shifts discharge temperature setting 9°C down
–008
Shifts discharge temperature setting 8°C down
0010
Shifts discharge temperature setting 10°C up
Temperature shift for
cooling / heating change in
auto heat / cool mode
0001
±1°C
0002
±2°C
0003
±3°C
0007
±7°C
(Upper limit)
Change to remote
control temperature
setting range
Cooling
0018
18°C (Lower limit at shipment)
0019
19°C
(Lower limit)
0029
29°C
0030
30°C (Upper limit at shipment)
(Upper limit)
Heating
0016
16°C (Lower limit at shipment)
0017
17°C
(Lower limit)
0029
29°C
0030
30°C (Upper limit at shipment)
(Upper limit)
Dr
ying
0018
18°C (Lower limit at shipment)
0019
19°C
(Lower limit)
0029
29°C
0030
30°C (Upper limit at shipment)
(Upper limit)
A
uto heat / cool
0017
17°C (Lower limit at shipment)
0018
18°C
(Lower limit)
0026
26°C
0027
27°C (Upper limit at shipment)
Humidifier operation
0000
Normal
0001
Ignore heat exchanger temperature conditions.
Filter (CN70) input
switching
0000
Filter input (differential pressure switch input)
0001
Alarm input (for trouble input about air cleaner or similar device)
0002
Humidifier input (Operates linked with drain pump when humidifier is
ON.)
Indoor unit electronic
control valve
0000
Present (Setting at shipment)
0002
None
T10 terminal switching
0000
Normal (Used as optional relay PCB or JEMA standard HA terminal.)
0001
Used for OFF reminder
0002
Fire prevention input
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 16
17/03/08 18:33:46
Содержание S-22MF2E5A8
Страница 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Страница 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Страница 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Страница 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Страница 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Страница 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Страница 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Страница 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...