5 - 17
2. Detailed Settings Function
5
VRF SYSTEMS Indoor Unit
Item code
Item
Setting data
No.
Description
Automatic drain pump
operation
0000 No forced operation
0001 Forced operation for 1 minute
0060 Continuous operation
Ventilation fan operation
0000 None
0001 Ventilation fan operated by remote controller.
Wired remote controller
sensor
0000 Not used. (Body sensor is used.)
0001 Remote control sensor is used.
“Operation change
control in progress”
display
0000 Normal (displayed)
0001 Not displayed
OFF reminder function
for when weekly timer is
used
0000 None
0001 Only stop time setting is enabled.
Discharge temperature
control
0000 Discharge temperature control OFF
0001 Discharge temperature control ON
Heat exchanger
temperature for cold air
discharge
(Heat exchanger control
point for control to
prevent cold air)
0013 Control temperature 13°C
0014 Control temperature 14°C
0025 Control temperature 25°C
0026 Control temperature 26°C
Fan output switching
0000 Output linked with fan. (ON when indoor unit fan is operating.)
0001 Fan mode operation output
Drain pump delayed
stop time
0000 No delayed stop
0001 1 second delayed stop
Except
Indoor unit
Type
U1, U2, Y2,
F2, T2, E2
1 minute delayed stop
Indoor
unit
Type
U1, U2, Y2,
F2, T2, E2
0002 2 seconds delayed stop
2 minutes delayed stop
0058 58 seconds delayed stop
58 minutes delayed stop
0059 59 seconds delayed stop
59 minutes delayed stop
0060 60 seconds delayed stop
60 minutes delayed stop
Humidifier setting
0000 Humidifier output OFF. Drain pump stopped.
0001 Humidifier output ON. Drain pump operates.
0002
Humidifier output ON. Drain pump operates for 1 minute when total humidifier
operating time reaches 60 minutes.
0003 Humidifier output ON. Drain pump stopped.
Flap operation mode
0000 Standard setting
0001 Draft reduction mode (Flap lower-limit position is shifted upwards.)
Flap swing mode
0000 Smudging reduction mode (Flap swing upper-limit position is shifted downwards.)
0001 Normal mode
0002 Draft reduction mode (Flap swing lower-limit position is upwards.)
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 17
17/03/08 18:33:46
Содержание S-22MF2E5A8
Страница 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Страница 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Страница 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Страница 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Страница 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Страница 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Страница 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Страница 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...