11. Electric Heater Control
12. Fan Control during Dry Mode
11. Electric Heater Control
The electric heater control is performed when an electric heater is installed with the indoor unit.
The heater turns ON when all of the following conditions (1 to 3) are satisfied in heating mode (thermostat ON).
①
Body sensor enabled: ON when T > 4.0˚C (Remote controller sensor enabled: ON when T > 2.0˚C)
OFF when T < 1.0 degree
②
ON: body sensor temperature < 26˚C, OFF: body sensor temperature > 29˚C
③
ON: discharge air temperature < 40˚C, OFF: discharge air temperature < 45˚C
ON
ON
OFF
Electric heater
+29
+26
Body sensor
(˚C)
+45
+40
Discharge air
(˚C)
+1
+4(+2)
(deg)
For details on T, refer to “1. Room Temperature Control”.
12. Fan Control during Dry Mode
The fan control during dry mode is as follows.
A
A
B
Fan mode
Set temp. in remote controller
+1
-1
T (deg)
A: Fan mode set in the remote controller
B: Fan mode is L during thermostat ON, LL during thermostat OFF
For details on T, refer to “1. Room Temperature Control”.
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 11
17/03/09 13:53:18
Содержание S-22MF2E5A8
Страница 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Страница 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Страница 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Страница 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Страница 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Страница 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Страница 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Страница 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...