7. Discharge Air Temperature Control
Discharge air temperature is controlled using the indoor unit discharge air temperature sensor. The discharge
air temperature is set in the EEPROM on the PCB. The setting is different depending on the model.
Discharge air temperature setting (at the time of factory shipment)
Indoor unit type
Discharge air temperature setting
Cooling
Heating
Y2, F2, M1, E2, K2, U2
12˚C
50˚C
E2 (FRESH AIR INTAKE MODE)
18˚C
45˚C
Condition for Thermostat ON
→
OFF under discharge air temperature control
①
Temperature less than “Discharge air temperature setting – 2˚C” is continuously detected for 20
minutes in cooling mode
②
Temperature more than “Discharge air temperature s 2˚C” is continuously detected for 20
minutes in heating mode
③
Temperature less than “Discharge air temperature setting – 3.5˚C” is continuously detected for 7
minutes in cooling mode
④
Temperature more than “Discharge air temperature s 3.5˚C” is continuously detected for 7
minutes in heating mode
There is no priority order between the room temperature control and discharge air temperature control.
Relation between thermostat ON / OFF and room temperature control / discharge air temperature control
Thermostat turns OFF: Either room temperature control or discharge air temperature control satisfies
thermostat OFF condition.
Thermostat turns ON: Both of room temperature control and discharge air temperature control satisfy
thermostat ON condition.
8. RAP Valve Kit Control
The RAP valve kit is sometimes used in the 2-Way system.
The RAP valve kit prevents refrigerant from collecting in the indoor heat exchanger when the indoor unit is
stopped. The following table shows the RAP valve kit operation.
Operating mode
RAP valve kit
Stopped
OFF
Fan
OFF
Cooling
Thermostat ON
OFF
Thermostat OFF
OFF
Heating
Thermostat ON
ON
Thermostat OFF
OFF
7. Discharge Air Temperature Control
8. RAP Valve Kit Control
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 9
17/03/09 13:53:17
Содержание S-22MF2E5A8
Страница 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Страница 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Страница 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Страница 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Страница 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Страница 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Страница 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Страница 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...