1-220
1
1-3. Refrigerant Flow Diagram
Indoor Unit
Outdoor Units
:
U-100PE1E5A
U-100PE1E8A
ø15.88
ø9.52
Compressor
Heat
EC
P
Defrost Temp
Expantion
valve
Cooling cycle
Heating cycle
exchanger
Heat exchanger
Temp Thermistor
Temp Thermistor
Outdoor-air
Discharge Temp
Thermistor
Suction Temp
Thermistor
4-way
valve
High pressure
switch
Thermistor
Accumulator
Muffler
Muffler
Strainer
Strainer
Heat
exchanger
Strainer
Distributor
Distributor
SM830231-02̲Single̲欧州.indb 220
SM830231-02̲Single̲欧州.indb 220
2014/09/19 13:21:38
2014/09/19 13:21:38
1
1-4. Operationg Range
Type PE1
Temperature
Indoor air intake temp.
Outdoor air intake temp.
Cooling
Maximum
Minimum
Heating
Maximum
Minimum
32°C DB / 25°C WB
18°C DB / 14°C WB
30°C DB / − WB
16°C DB / − WB
46°C DB
-15°C DB
24°C DB/18°C WB
-20°C DB / -20°C WB