1
1-316
Test Run Procedure
YES
YES
YES
NO
NO
NO
Recheck the items to check before the test run.
(See section “Items to Check Before
the Test Run” for Type K1.)
(See section “Basic wiring diagram”
for Type K1 (for Link Wiring).)
Check the combination (wiring) of indoor and outdoor units.
Is system “single-type”?
(1 indoor unit is connected
to 1 outdoor unit)
Are multiple outdoor units
used?
Set the outdoor unit system address.
Set the indoor unit control unit to “TEST”.
Can operation
be started?
Turn the power back ON to the
indoor unit.
Turn ON the indoor
and outdoor power.
Turn ON the indoor
and outdoor power.
(Automatic Address Setting)
(Automatic Address Setting)
Refer to “Table of Self-Diagnostic
Functions” to check the system.
In addition, refer to section “Automatic
Address Setting” for Type K1 (for Link
Wiring) and correct any items that need
to be corrected.
Note: Check the indoor-side drainage.
Set the automatic address
setting from outside unit.
Indicate (mark) the combination number.
(See section “Setting the outdoor unit system addresses”
for Type K1 (for Link Wiring).)
How to Set the Outdoor Unit System Address
(See section “Basic wiring diagram” and
“Setting the outdoor unit system addresses”
for Type K1 (for Link Wiring).)
How to Set Automatic Address
(See section “Checking indoor unit addresses”
and “Indicating (marking) the indoor and
outdoor unit combination number” for Type K1
(for Link Wiring).)
(See section “Checking indoor unit
addresses” for Type K1 (for Link Wiring).)
(See section “Test Run” for Type K1.)
See section “Table of Self-Diagnostic
Functions and Corrections (Type K1)”
for Type K1 (for Link Wiring).