1
1-267
1-10. Electrical Wiring
General Precautions on Wiring
(1)
(2)
(3)
(4)
(5)
(6)
or misoperation that occurs as a result of such unauthorized changes.
(7)
(8)
The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between units and ground the shield on both sides.
(9)
Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring
diagram.
Provide a power outlet to be used exclusively for each unit and a circuit breaker for overcurrent protection should be provided
in the exclusive line.
To prevent possible hazards from insulation failure, the unit must be grounded.
Each wiring connection must be done in accordance with the wiring system diagram. Wrong wiring may cause the unit to
misoperate or become damaged.
Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility for any damage
Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL ELECTRICAL
CODES before beginning.
You must ensure that installation complies with all relevant rules and regulations.
To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:
If the power supply cord of this appliance is damaged, it must be replaced by a repair shop designated by the manufacturer,
because special-purpose tools are required.
Recommended Wire Length and Wire Diameter for Power Supply System
Indoor unit
Control wiring
(C) Inter-unit
(between outdoor
and indoor units)
control wiring
(D) Remote control
wiring
(E) Control wiring
for group control
0.75 mm
2
(AWG #18)
Use shielded wiring*
0.75 mm
2
(AWG #18)
0.75 mm
2
(AWG #18)
Max. 1,000 m
Max. 500 m
Max. 200 m (Total)
NOTE
*
With ring-type wire terminal.
Indoor unit
Type
(B) Power supply Time delay fuse or
circuit capacity
2.5 mm
2
K1
Max.150 m
10A
CAUTION
Check local electrical codes and regulations before wiring.
Also, check any specified instruction or limitations.
SM830231-02̲Single̲欧州.indb 267
SM830231-02̲Single̲欧州.indb 267
2014/09/19 13:21:43
2014/09/19 13:21:43