1
1-324
(B) If there are obstacles at the discharge
More than 300
More than 300
More than
1000
Less than 500
(C)
If there is an obstacle that is higher than the unit on the intake side.
(There is no limit to the height of the obstacle above the discharge.)
If there are obstacles on both the intake and discharge
Pattern 1
More than
300
More than
100
• The dimensions for H, A and L are shown in the following table.
L
A
L H
0 < L
1/2 H
300
1/2H < L H
500
H < L
Install a pedestal or mount so that L
H
L
A
L H
0 < L
1/2 H
500
1/2H < L H
750
H < L
Install a pedestal or mount so that L
H
• Cover the bottom part of the pedestal or mount
so that air does not go through it.
Less than 500
More than
1000
More than 200
More than 500
Less than 500
More than
1000
More than 500
More than
200
More than
500
Less than 500
More than
1000
More than 200
• The dimensions for H, A and L are shown in the following table.
• Cover the bottom part of the pedestal or mount
so that air does not bypass it.
• A limit of only 2 units can be installed.
If the upper part is open
If the upper part is open
If there are obstacles above the unit
If there are obstacles above the unit
1
For separate installation location
1
For separate installation location
1
For separate installation location
2
For multiple units (up to 2 units)
1
For separate installation location
2
For multiple units (more than 2 units)
2
For multiple units (more than 2 units)
2
For multiple units (more than 2 units)
More than 300
More than 500
(unit: mm)
(unit: mm)
(unit: mm)
(unit: mm)
More than 300
More than
1000
Less than 500
Less than 500
More than
1000
More than 500
More than
300
More than
100
More than
200
More than
500
Less than 500
More than
1000
More than 200
Less than 500
More than
1000
More than 200