40
AHU Kit – Installation Instructions – 07/2023
Installation
4
3. Open the front-side door of the enclosure as shown below (left), and mount the backside of
the enclosure to the wall or surface using field-supplied fixing screws inserted through the
previously prepared holes at each corner as shown below (right).
4. Screw the cable glands, which are supplied loose, into the openings at the bottom of the
enclosure.
ATTENTION
Signal errors through noise from live power supply cords
Power supply cords can generate noise, which may cause signal errors, if they are run in close
proximity to any extra-low voltage control wiring.
►
Keep 230 V AC power supply wiring apart from the extra-low voltage control wiring for
sensors etc.
► Route 230 V AC power supply wiring through different cable glands than the extra-low
voltage control wiring.
5. Insert the wiring from below the enclosure through the screwed cable glands and connect the
wires to the terminal block as required.
6.
Having finished wiring of the AHU Kit, close the front-side door of the enclosure and proceed
with the installation of all other required system components (see →
4.2 Installation of
expansion valve, p. 41
and →
4.3 Installation of thermistors, p. 42
). The AHU Kit will then
be ready for matching the outdoor unit capacity with AHU Kit capacity (see →
4.4 Matching
outdoor unit capacity with AHU Kit capacity, p. 46
).
!
Содержание PAW-160MAH3M
Страница 2: ...Notes...
Страница 90: ...90 AHU Kit Installation Instructions 07 2023 Parameter settings 9 Notes...
Страница 91: ...Notes...