56
AHU Kit – Installation Instructions – 07/2023
Electrical Wiring
5
Terminal No.
Allocation
Function
Description
X4
l
TA1
X4.1
No polarity
Suction Temperature Sensor TA input (included)
(Room Temperature Sensor)
Air temperature sensor
l
TA2
X4.2
No polarity
l
E1.1
X4.3
No polarity
Sensor E1 / TH2 input
(included)
Refrigerant temperature sensor
l
E1.2
X4.4
No polarity
l
E3.1
X4.5
No polarity
Sensor E3 / TH4 input
(included)
Refrigerant temperature sensor
l
E3.2
X4.6
No polarity
l
BL1
X4.7
No polarity
Discharge Temperature Sensor BL
Input (included)
Air temperature sensor
l
BL2
X4.8
No polarity
l
OP1
X4.9
COM for OP2 - OP6 Higher
Potential
+ 12 V DC
12 V DC relay required for each signal output, field supplied
l
OP2
X4.10
Lower Potential for Defrost
Defrost signal output
l
OP3
X4.11
Lower Potential for Thermostat
ON
Thermostat ON signal output
l
OP4
X4.12
Lower Potential for Cool
Operation
Cool operation signal output
l
OP5
X4.13
Lower Potential for Heat
Operation
Heat operation signal output
l
OP6
X4.14
Lower Potential for Fan Mode
Operation
Fan mode (free cooling) operation signal output
l
MO1
X4.15
ORG
Expansion valve output
l
MO2
X4.16
RED
l
MO3
X4.17
YEL
l
MO4
X4.18
BLK
l
MO5
X4.19
GRY / WHT
Terminal No.
Allocation
Function
Description
X5
l
U1
X5.1
No polarity
Communication bus wiring P-link
Required for communication with outdoor unit and centralised
controller
l
U2
X5.2
No polarity
l
R1
X5.3
No polarity
Terminal for Group Wiring (RC connection)
Internal Potential: 16 V DC between R1 & R2
l
R2
X5.4
No polarity
To be continued on next page.