33
AHU Kit – Installation Instructions – 07/2023
Product description
3
System example for PACi and PACi NX single-connection system
PACi NX outdoor unit
Piping
Outdoor unit /
indoor unit wiring
Wiring for
temperature sensors
Air Handling Unit
PAW-280PAH3M-1
3.5 Technical data
Technical data – AHU Kit
MAH3 / PAH3 generation
Power source
V / ph / Hz
220 ... 240 / 1 / 50
Rated current consumption
A
0.1
Rated power consumption (max.)
W
18.0
Dimensions (enclosure)
H x W x D
mm
500 x 400 x 150
Net weight (without valves)
kg
11.5
Ambient temperature (max.)
°C
45
Protection class
IP65
Dimensions – AHU Kit
MAH3 / PAH3 generation
500
400
129
150
125
125
250
20
20
360
460
Front view
Right side view
Left side view
Top view
Rear view
Содержание PAW-160MAH3M