36
AHU Kit – Installation Instructions – 07/2023
Product description
3
Calculation example for number of passes in the heat exchanger
The minimum number of passes in the AHU heat exchanger is restricted. The limit is calculated by
the formula:
Minimum number of passes
= Number of steps × Distance between tube sheets × Number of rows × 1.5 × 10
–4
The calculated value must then be rounded up to the next integer number.
Example
Number of steps: 12
Distance between tube sheets: 1,000 mm
Number of row: 3
Minimum number of passes = 12 × 1,000 x 3 × 1.5 × 10
–4
= 5.4
This value must be rounded up to 6.
This means that the minimum number of passes is 6 passes.
Technical data and limitations – PACi NX systems –
R32
AHU Kit model
PAW-280PAH3M-1
Outdoor unit – PACi NX Standard
U-25PZ3E5
U-36PZ3E5
U-50PZ3E5 U-60PZ3E5A U-71PZ3E5A U-100PZ3E5/8 U-125PZ3E5/8 U-140PZ3E5/8
Nominal cooling capacity
kW
2.5
3.6
5.0
6.0
7.1
10.0
12.5
14.0
Nominal heating capacity
kW
3.2
3.6
5.0
6.0
7.1
10.0
12.5
14.0
Piping connections
Liquid pipe
Inch (mm)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
1/4 (6.35)
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
Gas pipe
Inch (mm)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
1/2 (12.70)
5/8 (15.88)
5/8 (15.88)
5/8 (15.88)
5/8 (15.88)
Piping length
Min / Max
m
3 / 15
3 / 15
3 / 20
3 / 40
3 / 40
5 / 50
5 / 50
5 / 50
Precharged length (
R32
)
Max
m
7.5
7.5
7.5
30
30
30
30
30
Additional refrigerant charge (
R32
) due to extended piping
length
kg/m
0.01
0.01
0.015
0.015
0.017
0.045
0.045
0.045
Ambient temperature (outdoor unit)
Cooling (Min / Max) °C DB
-10 / +43
-10 / +43
-10 / +43
-10 / +43
-10 / +43
-10 / +43
-10 / +43
-10 / +43
Heating (Min / Max) °C WB
-15 / +24
-15 / +24
-15 / +24
-15 / +24
-15 / +24
-15 / +24
-15 / +24
-15 / +24
AHU unit under “standard conditions”
Air volume flow
Cooling (Min / Max) m³/h
360 / 570
540 / 870
630 / 990
780 / 1,320
780 / 1,320
900 / 2,160 1,140 / 2,280 1,200 / 2,400
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
18 / 32
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU DX coil heat exchanger volume Min / Max
dm
3
1.0 / 1.12
1.00 / 1.121
1.00 / 1.121
1.3 / 1.4
1.3 / 1.4
1.7 / 1.9
1.7 / 1.9
1.7 / 1.9
Heat exchanger face area
Min / Max
m
2
– / –
– / –
– / –
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
0.43 / 0.51
AHU unit under “special conditions A”
2
Air volume flow,
subject to restrictions
2
Cooling (Min / Max) m³/h
360 / 870
540 / 870
630 / 1,000
780 / 1,450
780 / 1,600
900 / 2,300 1,140 / 2,520 1,200 / 2,640
Air intake temperature
1
Cooling (Min / Max) °C DB
18 / 32
18 / 32
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
18 / 30
°C WB
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
14 / 25
Heating (Min / Max) °C DB
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
16 / 30
AHU unit under “special conditions B”
3
AHU DX coil heat exchanger volume,
subject to restrictions
3
Min / Max
dm
3
1.0 / 1.2
1.0 / 1.2
1.0 / 1.2
1.3 / 1.6
1.3 / 1.6
1.7 / 2.6
1.7 / 2.6
1.7 / 2.8
Additional refrigerant charge (
R32
) due to larger heat
exchanger volume
kg/dm
3
0.83
0.83
0.83
0.83
0.83
0.83
0.83
0.83
Max. additional refrigerant charge (
R32
)
kg
0.07
0.07
0.07
0.17
0.17
0.58
0.58
0.74
Max. pipe length
m
7.5
7.5
15
25
30
35
35
35
Max. ambient temp. for pump down
°C DB
n/a
n/a
30
30
30
30
30
30
Continued on the following page. See footnotes overleaf.