50
AHU Kit – Installation Instructions – 07/2023
Installation
4
7. Once the setting procedure is completed, exit the “Detailed settings” mode by pressing the
“MENU” button several times. This will invoke a confirmation message (see below). Select
“YES” with the “UP” and “DOWN” buttons, and then press the “ENTER” button to finish the
“Detailed settings” mode and return to the normal remote controller screen.
Detailed settings
[
]
[
]
Set data
1-1
10
0001
0001
Unit no.s
Code no.
?
Exit detailed
settings
estart
and r
YES
NO
Method D: Ignoring PACi outdoor unit capacity
The last possibility is to ignore the capacity of the currently used PACi outdoor unit.
Important
Method D is only applicable to the following combinations of PACi outdoor units and AHU Kits:
●
PACi NX PZ3/PZH3/PZH4 outdoor units (R32) and PAH3 AHU Kit model
To change the relevant setting, invoke the “Detailed settings” mode on the AHU Kit’s integrated
remote controller (CZ-RTC6BL).
1. Verify that the display of the integrated remote controller is working, then stop the system and
power it on again before performing the following steps.
2. Simultaneously press and hold the relevant three-button combination on the remote controller
(see below) for at least 4 seconds, until the “Maintenance func” screen appears on the display.
Note:
This step has to be performed within 30 seconds after powering on the system while auto-
addressing is in progress and the message “Assigning” is shown on the display, otherwise error
E16 will occur. In this case, repeat steps 1 and 2 and mind the time limit.
NX
i
Содержание PAW-160MAH3M
Страница 2: ...Notes...
Страница 90: ...90 AHU Kit Installation Instructions 07 2023 Parameter settings 9 Notes...
Страница 91: ...Notes...