No. SX-DSV02829 -
195-
*2. After Internal control power supply, protective functions are active from approx. 1.5 sec after the start of
initializing microcomputer. Please set the signals, especially for protective function, for example over-travel
inhibit input (POT, NOT) or feedback scale input, so as to decide their logic until this term. The lapse time can
be changed with Pr 6.18 “Wait time after power-up”.
*3. If Err 61.2 “Magnet pole position estimation error 3 protection” is activated or with Pr 9.20 = 0, the magnet pole
position estimation completion output will not turn ON. The timing (condition) at which the magnet pole
position estimation completion output turns ON depends on the setup value for Pr 9.20 “Magnet pole detection
scheme selection”. For more information, refer to Section 2-2
*4. A brake release output (BRK-OFF) is different from the set brake of 60FEh via EtherCAT communication.
*5. The set brake output is output controlled by the set brake of 60FEh via EtherCAT communication.
For information on the set brake output details, refer to the section 6-9-3 in the Technical Reference EtherCAT
Communication Specification (SX-DSV02830).
The set brake output can be released in the servo-off state.Therefore, In consideration of safety, please control
the set brake output.