No. SX-DSV02472 -
114-
Error No.
Protective function
Causes
Measures
Maiin
Sub
91
1
command error
protection
• Control mode was switched at intervals shorter than 2
ms.
• Check the process of upper device.
92
0
Encoder data
recovery error
protection
In the absolute mode with semi-closed control, internal
position data has not been correctly initialized.
• Regulate the power source of the encoder to 5 VDC
±
5%
(4.75
−
5.25 V). Measure the voltage at the encoder cable
end if it is long.
• If the motor cable and encoder cable are bundled together,
separated them.
• Connect the shield to FG.
1
External scale
data recovery
error
protection
(Not supported)
In the absolute mode with full-closed control, internal posit
ion data has not been correctly initialized.
• Regulate the power source of the external scale to 5 VDC
±
5% (4.75
−
5.25 V).
…
Measure the voltage at the external
scale connection cable end if it is long.
• If the motor cable and external scale connection cable are
bundled together, separated them.
• Connect the shield to FG.
…
See the external scale conne
ction diagram. in Reference specification SX-DSV2201.
93
0
Parameter setup
error protection 1
Manufacturer's use of the parameter setting is incorrect.
Please do not modify the parameter manufacturer's use.
2
Parameter setup
error protection 2
External scale ratio exceeds acceptable range.
• Check the parameter setting value.
• External scale ratio must be in the range 1/40 to 160.
3
External scale
connection error
protection
(Not supported)
The communication type of the connected external scale
(serial communication model) does not match the type
selected through Pr 3.23 External scale selection.
• Set Pr 3.23 to the type of external scale connected.
7
Parameter setup
error protection 5
Manufacturer's use of the parameter setting is incorrect.
Please do not modify the parameter manufacturer's use.
95
0–4
Motor automatic
recognition error
protection
The motor and the driver have not been matched.
Replace the motor which matches to the driver.
98
4
Unusual
communication IC
initialization
protection
There is an abnormality in the initialization process
of the communication IC.
- Turn the power off once, then on again.
- Nevertheless, if the error is out of view, there is
a possibility of failure. Discontinue use, please replace the
motor, the servo amplifier.
- Be returned to the sales agent survey (repair).
Other No.
Other error
protection
Control circuit has malfunctioned due to excess noise or
other causes.
Some error has occurred inside of the driver while
triggering self-diagnosis function of the driver.
• Turn off the power once, then re-enter.
• If error repeats, this might be a failure. Stop using the
products, and replace the motor and the driver. Return the
products to the dealer or manufacturer.
R1.05
Motor Business Division, Appliances Company, Panasonic Corporation