3
.
Evacuation
3.1
Leak check of connection point
Preparation: Leak check spray (liquid detergent may be used), dedicated GM, general
purpose GM *, powerful vacuum pump, Nitrogen cylinder, charge hose,
branching equipment, tools
* In case of evacuating simultaneously on the low temperature side and the
high temperature side
Procedure: Connect as shown below and prepare for vacuum evacuation. When repairing
on the low temperature side was also done, add general purpose GM and
connect. ← Vacuum exhaust at the same time at high temperature and low
temperature for shortening the time
(In the case of only the high temperature side, connect the hose from the
nitrogen cylinder directly to the refrigerant port)
Open the unopened valves of nitrogen cylinders, VR, VL, VH and general
purpose GM,
Perform a leak check of the connection point. (Nitrogen replacement: provided
that the secondary pressure is 0.5 to 0.7 MPa)
Note
:
Use a leak check spray to check the gas leak at the connection point.
Generally, the explosion-proof vacuum pump has a small capacity, so prepare a
separate powerful vacuum pump.
(All flammable HC refrigerants are released, so there is no problem even if they are
not explosion-proof type)
Connection should be made surely without leakage.
Valve sate
open
shut
VC
○
VG
○
VL
○
VH
○
VR
○
Charge hose
Low pressure
service valve
High pressure
service valve
Low temp.
低温側
Nitrogen cylinder
General GM
Charge hose
VR
VG
VL
VC
VH
Refrigerant
port
Vacuum
port
High pressure
service port
Low pressure
service port
Dedicated GM
Explosion-proof
vacuum pump
-44-
Содержание MDF-DU502VH
Страница 8: ...Dimension MDF DU502VH 5 ...
Страница 9: ...MDF DU702VH 6 ...
Страница 17: ...Wiring Diagram 14 ...
Страница 18: ...main Circuit Diagram 15 ...
Страница 19: ...power 16 ...
Страница 20: ...USB 17 ...
Страница 73: ...WIRING YG Y Y GR B G W W W Y G R BL Y W R R BL R OR B BL R OR B Y W Y G Y G R BL 70 ...