96
Installation Manual
8-5. Checking Test Run Results
Check whether the test run was completed normally.
■
Preparation
•
Set the storage battery system to the stopped state in the normal state. The system can only be switched to the
parameter setting mode while it is in a stopped state.
■
Operation Procedure
8-6. Checking Battery Lot Number and Inverter Communication Status
•
The first and second digit indicate the results of the Reverse Current CT test and Stand-alone test, respectively.
•
Press "CLOCK (▼)"+"DATA (▲)" for three seconds in the normal state to open the status selection mode.
•
Press "DATA (▲)" or "CLOCK (▼)" to display the test run status (S2).
•
The results would be [ ] for completion and [ ] if incomplete.
•
The actual operations cannot be performed unless the Reverse Current CT test and Stand-alone test results were
both completed normally.
•
While the Status selection mode is selected, press "DATA (▲)" or "CLOCK (▼)" to display the test run status (S3).
•
The first and second digits indicate the results of the Battery Lot Number Status and Inverter Communication Status
Communication Status, respectively.
The results would be [
•
], check Battery serial number (See 3-2 Checking the battery lot number).
] for completion and [
•
Please contact the distributor if the numbers do not match.
•
If 1st digit is not [
] if incomplete.
Stopped (Grid-connected)
Stopped (Stand-alone)
Status 2
Status 1
Status 3
ュモヵモ
ヤロヰヤレ
or
ュモヵモ
ヤロヰヤレ
or
ュモヵモ
ヤロヰヤレ
or
Status Selection
Normal State
ヰワバ
ヰョョ
ヤモワヤユロ
1 sec
3 sec
ヤロヰヤレ
+
: completion
: Incomplete
1st digit : Reverse Current CT Test
2nd digit : Stand-alone Operation Test
: completion
: Incomplete
1st digit : Battery Lot Number Status
2nd digit : Inverter Communication Status
by qualified personnel.
properly configured.
9. Checking the Network Adaptor Connections
9-1. Checking the Network Adaptor Connections
In order to connect this system to the server via the Network Adaptor to perform remote controls, etc., the
communications with the Network Adaptor must be operating normally. Otherwise, the remote control instructions, etc.
from the server cannot be accepted.
● The DR control instructions, etc. from the server cannot be accepted if the communications with the Network
Adaptor are not
● The work must be performed
9-2. Starting Up the Network Adaptor
■
Preparation
•
Switch the DC Protector (
) and protection device for the storage battery system to ON.
(
)
■
Operation Procedure
•
Switch ON the protection device for Network Adaptor.(
)
The Network Adaptor launches and starts communicating with the storage battery system.
CT
CT
L
N1
N
L1
COM
COM
PE
PE
PE
Switch board
N
L
PE
N
Stand-alone
Socket-outlet
(Type-02)
Turn off these protection
devices in an emergency.
Network
Adaptor
Main
switch
Point of
Supply
TN or TT
system
Storage
battery
system
DC Protector
DC Protector
SB
SB
2
SB
1
SB
1
DRED
SYS
Protection
device for
Storage
battery
system
Protection
device for
Network
Adaptor