7-17. Characteristic Power Factor Curve Setting
※
This mode is enabled only when it is set to the MODE4 as described in Chapter 7-13.
With this mode can be changed along the power factor on the output. Setting the way is as follows.
①
While the power inputs the inverter, the power factor is set ’ 1’.
②
When the power output is from 0[W] to Characteristic Power(P1)
X Rated Power[W], the power factor is set ’
cosφ of point1 (λ1)’.
③
When the power output is from Characteristic Power(P1)
X Rated Power[W] to Characteristic Power(P2)
X Rated Power[W], the power factor is set ’ cosφ of point1 (λ1)’ at Characteristic Power(P1)
X Rated Power[W]
and the power factor is set ’ cosφ of point2 (λ2)’ at Characteristic Power(P2)
X Rated Power[W].
As ’cosφ of point1 (λ1)’ at Characteristic Power(P1)
X Rated Power[W] and ’cosφ of point2 (λ2)’ at
Characteristic Power(P2)
X Rated Power[W], the power factor is calculated by the proportional calculation.
④
When the power output is from Characteristic Power(P2)
X rated Power[W] to Rated Power[W], the power factor
is set ’ cosφ of point2 (λ2)’ .
※
Characteristic Power (P2) should be set to be equal to or greater than Characteristic Power (P1).
cosΦ
0.8
0.8
0
①
②
③
④
Power(P/P Rated)
Leadin
g
Lagging
Parameter Item
Default Set Point
Range
Parameter Selection
Display
0.00
1.00
LAGG
1.00
1.00
LAGG
0.00
〜
1.00
0.90
〜
1.00
LAGG
/LEAD
0.00
〜
1.00
0.90
〜
1.00
LAGG
/LEAD
Characteristic
Power (P1)
Cosφ of Point1
(λ1)
Source or Sink
Setting(λ1)
Characteristic
Power (P2)
Cosφ of Point2
(λ2)
Source or Sink
Setting (λ2)
Table Characteristic Power Factor Setting Parameter List