Chapter 3 Function
3-29
3
Analog Scaling
This function scales analog current output or analog voltage output to any
desired value.
Measurement values A and B on any two measurement point can be scaled with
currents a and b or voltages a and b on any two points. Analog output is turned ON
according to the scaling set for analog output selection.
Item
Panel
display
Setting
range
Function
Initial value
Meas A
-95000 to
+95000
Negative
measurement range
Meas B
-95000 to
+95000
Positive
measurement range
Current a
(*1)
+4.000 to
20.000
Current b
(*1)
+4.000 to
20.000
Voltage a
(*2)
0 to +10.000
Voltage b
(*2)
0 to +10.000
Make
measurement
value, current,
and voltage
settings.
*1 Not displayed when "Voltage" is selected for "Analog Output Selection."
*2 Not displayed when "Current" is selected for "Analog Output Selection."
Supplemental remarks
The following default measurement values A and B apply.
Diffuse reflection
Specular reflection
Type
Meas. Val A
Meas. Val B
Meas. Val A
Meas. Val B
30 mm
-4 mm
+4 mm
-2 mm
+2 mm
50 mm
-10 mm
+10 mm
-5 mm
+5 mm
85 mm
-20 mm
+20 mm
-10 mm
+10 mm
120 mm
-60 mm
+60 mm
-
-
250 mm
-150 mm
+150 mm
-
-
Measurement range
Analog output
b
b’
a
a’
Current voltage [V]/Current [mA]
Voltage [V]/Current [mA]
: Voltage/Current before change
: Voltage/Current after change
Measurement value A
Measurement value B