20
Operation Manual
FT1020G3 Rev 2.10.4
the key in the display, the key has no function
P9 Several Alarms
Grey
Used when LEDs "Several Alarms" (L6) are lit, scroll
through the queued alarm points or zone-addresses. For
more details, see chapter "Fire alarm" page 58.
Note:
To scroll/browse through the queued zones, use
the soft key "Next zone" (P5).
3.4.1.2 FT1020G3 Display CP Indicators
Table 5 LED indicators on Control Panel (CP)
No. LED Indicator
Colour Indicating
L7
System fault
Yellow
FT1020G3 is not running due to one of the following:
•
S/W fault
•
CPU fault
•
Memory fault
•
No contact between main board and MMI board
•
FDCIE restart (fault code ≠ 00 / 03 / 25 / 50 / 53)
L8
Test mode
Yellow
One or more zones are in "test mode", see page 110 &
Fault / Disablements
L9
General fault
Yellow
Fault(s) in the system, i.e. not acknowledged fault(s) and /
or not corrected fault(s)
. See also page 146.
L10 General
disablements
Yellow
Disablement(s) in the system.
L11 Alarm devices
Yellow
Steady
: Output(s) type "Alarm devices" are disabled.
Flashing
: Output(s) type "Alarm devices" have generated
fault(s).
This is also valid when the FDCIE has no "contact" with a
unit with such an output, e.g. 3379, 4487, etc.
L12 Fire brigade TX
Yellow
Steady
: Output(s) for "ASE" disabled
Flashing
: ASE (routing equipment) power supply output
or one or more supervised outputs (of type "Routing
equipment" have generated fault(s). This is also valid
when the FDCIE has lost "contact" with a unit with such an
output, e.g. 4461.
ASE (routing equipment)
L13 Fault TX
activated
Yellow
One or more of faults not serviced
.
Output "Fault condition" for fault TX (routing equipment) is
activated.
Test of routing equipment in progress (see menu H1).
Sensitive fault detection mode is on (see menu H5/A2).
L14 Fire brigade TX
delay
Yellow
The
A
lert
A
nnunciation function is enabled.
Note
: Acknowledged alarm and isolated alarm are used only in the NZ convention.
10
The soft key “P8” has the function Alert Annunciation Acknowledge, if a COM loop unit is configured for alert annunciation.
11
Serviced fault will clear if the fault is set to non-latching in the system properties
12
Serviced fault will clear if the fault is set to non-latching in the system properties
13
Main board 5012 Terminal Block "J3:3-4", fuse F8 (T500mA 250 V – 5 x 20mm Ceramic).
14
See also chapter “Fault acknowledge”
Содержание Firetracker FT1020G3 CIE
Страница 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Страница 2: ...This page has deliberately been left blank...
Страница 174: ...174 Operation Manual FT1020G3 Rev 2 10 4 Figure 22 19 Rack 22U FT1020G3 General Arrangement with 6U battery box...
Страница 175: ...175 Operation Manual FT1020G3 Rev 2 10 4 Figure 23 19 Rack 13U FT1020G3 General Arrangement with 6U battery box...
Страница 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Страница 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...