The download will not be completed until the following box is shown:
7. Click “
OK
”
After the SSD download, the FT1020G3 will restart. A number of faults may then be
generated due to the loop units being not connected yet. This will cause "heavy traffic" on
the network, which might affect and delay the SSD download to the other units.
Disconnected at start up
In the COM loop properties dialog box, the "
Disconnected at start up
" check box can be
selected. The COM loop will then be disabled directly after the download restarts and
therefore no faults will be generated.
Note: A COM loop "Disconnected at start up" can be re-connected via menu H8/S1 but it
will be disconnected again after next SSD download. Finally, the SSD for that Control Unit
has to be downloaded again with the option "Disconnected at start up" not selected.
For more details, refer to EBLWin “Help” instructions.